5. After that, detach control switches of the cooktop. Make setting by
turning the screw in the middle of gas cocks with a small screwdriver in
the manner shown in the following picture. To adjust ow rate screw, use
a screwdriver having suitable dimension. For LPG, turn the screw clockwise.
For natural gas, turn the screw one time counter clockwise. At low
position, length of normal ame should be 6-7 mm. For the last control,
check out whether ame is open or closed.
Setting of your appliance may differ according to the type of gas cock used.
Ventilation Of Room
The air needed for burning is received from room air and the gases emitted
are given directly in room. For safe operation of your product, good room
ventilation is a precondition. If no window or room to be utilized for room
ventilation is available, additional ventilation should be installed. However,
room has a door opening outside, it is no needed to vent holes.
Room size Ventilating opening
Smaller than 5 m³ min. 100 cm²
Between 5 m³ - 10 m³ min. 50 cm²
Bigger than 10 m³ no need
In basement or cellar min. 65 cm²
Figure 4 Figure 5