84 Part Number: 000015431 Rev 02 6/20
E09 Flooding Evaporator Fault Single Evaporator, Single
Circuit
Average compressor discharge line temperature during
the first 6 minutes of the freeze cycle (T2) compared to the
average of the Prechill (T1) +50°F is less than 1.05°F.
E10 Flooding Evaporator Fault Dual TXV, Dual Circuit
Average compressor discharge line temperature during
the first 6 minutes of the freeze cycle (T2) compared to the
average of the Prechill (T1) +50°F is less than 1.05°F.
E11 Refrigeration Fault
The compressor discharge temperature did not increase
by at least 10° F, and the evaporator temperature did not
decreased by at least 10° F - Measured from Refrigeration
Start up or Prechill until 2 minutes into the Freeze cycle.
E12 Curtain Switch Fault Open more than 24 hours
The ice machine is set to ice making and remains in bin
full condition for more than 24 hours. The curtain switch is
open or curtain is off.
E13 Spare
E14 Spare
E15 Fan Cycle Control Fault - Low Liquid Line Temperature
The liquid line temperature dropped below 60° F for more
than one continuous minute during the freeze cycle.
E16 Remote Condensing Unit Fault (CVD Only)
The liquid line temperature dropped below 40° F, or
exceeded 140° F for more than 1 continuous minute during
the freeze cycle.
E17 Spare
E18 Spare