54 Outside Unit
Test Run
Sensor checking function judges whether the current temperature of indoor and outdoor unit sensors is right or
not. It checks 3 indoor temperature sensors, 9 outdoor temperature sensors, 2 outdoor pressure sensors.
It is used for judging sensor abnormality. Note 2)
Note 1)
Sensor Checking Function (U3 Chassis, 2Fan Model)
Wait for 3 min. after power
reset
Note 3)
Start
Main PCB
SW01S
Set the DIP S/W according to the function
Sensor Checking
Refrigerant Auto Charging : 1,2,7 ON
Sensor Checking
Refrigerant Checking : 1,2,7,14 ON
Main PCB
SW01B
SW02B
Press the black button for 2 sec. on main PCB.
Main PCB
SW01V
Indoor/Outdoor units operate with
air circulation mode
Refrigerant Auto Charging
Press the black button
until '508' is displayed
Judging sensor
normality
Error Display
Refrigerant
Auto Charging
Main pcb
LED
Note 4)
Press the black button on the main PCB for 2 sec.
Main PCB
SW01V
Press the black button for 2 sec. after turning off all
of DIP S/W.
Refrigerant Checking
Press the black button
until '608' is displayed.
Refrigerant
Checking
Dont Perform Sensor Checking
No
Yes
Yes
No
Completed.
Note
1. Sensor checking function is used with Refrigerant
Checking and Refrigerant Auto Charging.
2. Check abnormal sensor
3.
It is displayed at the LED on the main PCB at each step.
4. Refer to the next page for sensor error code part
Would you perform
the Sensor
checking?
Caution
1. Confirm auto addressing has been performed (Check installed number of IDU).
2. The error can be displayed even if the sensor is normal according to installation and temperature condition.
If error occurs, check the sensor and judge abnormality.