SurgeX UPS-1000-OL Standalone Battery Backup

User Manual - Page 20

For UPS-1000-OL. Also, The document are for others SurgeX models: UPS-2000-OL, UPS-3000-OL

PDF File Manual, 44 pages, Read Online | Download pdf file

UPS-1000-OL photo
Loading ...
Loading ...
Loading ...
© 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 17
4.2.3 Output Frequency Setting (Item 03)
Interface
Setting
You may set the initial frequency on battery mode:
50: output frequency is 50Hz
60: output frequency is 60Hz
If converter mode is enabled, the following output frequency can be chosen:
50: output frequency is 50Hz
60: output frequency is 60Hz
4.2.4 Bypass Mode Enable /Disable when the UPS is off (Item 06)
Interface
Setting
ENA: Bypass mode is enabled when the UPS is turned off. When the UPS is
first plugged in, it will enter bypass mode, or if the UPS is in on-line mode
and then turned off, it will enter bypass mode.
DIS: Bypass mode is disabled when the UPS is turned off. When the UPS is
first plugged in, it will enter standby mode with no output, or if the UPS is
in on-line mode and then turned off , it will enter standby mode with no out-
put.
4.2.5 Programmable Outlets Enable /Disable (Item 07)
Interface
Setting
ENA: Programmable outlets are enabled. When the UPS goes to Battery
mode the programmable outlets will supply power to the connected load for a
duration equal to the timer setting in section 4.2.6 or until the battery be-
comes depleted, whichever occurs first.
DIS: Programmable outlets are disabled. When the UPS goes to battery mode
the programmable outlets will supply power to the connected load until the
battery becomes depleted.
Loading ...
Loading ...
Loading ...