SurgeX UPS-1000-OL Standalone Battery Backup

User Manual - Page 19

For UPS-1000-OL. Also, The document are for others SurgeX models: UPS-2000-OL, UPS-3000-OL

PDF File Manual, 44 pages, Read Online | Download pdf file

UPS-1000-OL photo
Loading ...
Loading ...
Loading ...
© 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 16
1. Press and hold the “SELECT” button for at least five seconds to enter the UPS setting mode.
2. Press the “UP” or the “DOWN” button to scroll thru all of the parameters itemized as (01, 02, 03, 06, 07, 08,
09, 10 and 11).
3. When you see the item of the parameter that you want changed press the “LEFT ARROW” button. In the
“Setting Operation” window on the LCD display the item will blink depending on the selected parameter.
4. Press the “UP” or the “DOWN” button to scroll thru all of the available settings for that parameter.
5. When you see the setting that you want for that parameter press the “LEFT ARROW” button to choose
that setting.
6. To exit the UPS setting mode press the UP” or DOWN” button and scroll to the ESCAPE function (item 00).
7. Press the “LEFT ARROW” button.
4.2.1 Output Voltage Setting (Item 01)
Interface
Setting
The following output voltage can be chosen for on-line mode operation:
100 - 120 Volt Models
100: Output Voltage is 100VAC
110: Output Voltage is 110VAC
115: Output Voltage is 115VAC
120: Output Voltage is 120VAC
4.2.2 Frequency Converter Enable/Disable (Item 02)
Interface
Setting
ENA: frequency converter mode is enabled. When the input frequency is at
or between 40Hz to 70Hz the output frequency will be constant and equal to
the value (50 Hz or 60Hz) chosen in section 4.2.3 and the output voltage will
be constant and equal to the value chosen in section 4.2.1. The bypass will be
disabled in this mode.
DIS: converter mode is disabled. The output frequency is equal to the input
frequency and the output voltage will be equal to the value chosen in section
4.2.1.
Loading ...
Loading ...
Loading ...