SurgeX UPS-1000-OL Standalone Battery Backup

User Manual - Page 18

For UPS-1000-OL. Also, The document are for others SurgeX models: UPS-2000-OL, UPS-3000-OL

PDF File Manual, 44 pages, Read Online | Download pdf file

UPS-1000-OL photo
Loading ...
Loading ...
Loading ...
© 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 15
4.
Setting Up UPS Parameters
4.1
Factory Default Settings
The UPS is shipped with the following default factory settings. Refer to the table below and also to the table “LCD
Display Abbreviation Index” in Section 9.3.
PARAMETER
FACTORY DEFAULT SETTING
100 - 120 Volt Models
Output Voltage
120
Frequency Converter
DIS
Output Frequency
60
Bypass Mode
ENA
Programmable Outlets
DIS
Programmable Outlets Backup Time Setting
2
LCD Display Direction Setting
RAC
Acceptable Input Voltage Range Setting
85-135
Number of External Battery Packs
0
If the factory default settings are acceptable, proceed directly to Section 5 “UPS OPERATION”.
To change any of the default settings proceed directly to Section 4.2 “Changing Default Settings”.
4.2
Changing Default Settings
Plug the input of the UPS into a two-pole, three-wire, grounded receptacle. Avoid using extension cords. If the
mains voltage is within the acceptable range, the UPS will enter bypass mode. “BYPASS” will be displayed in the
UPS status window on the LCD display.
LCD Display in Bypass Mode
Rack Display
NOTE: The LCD will display the actual input voltage in the input/output and battery window.
Loading ...
Loading ...
Loading ...