SurgeX UPS-1000-OL Standalone Battery Backup

User Manual - Page 17

For UPS-1000-OL. Also, The document are for others SurgeX models: UPS-2000-OL, UPS-3000-OL

PDF File Manual, 44 pages, Read Online | Download pdf file

UPS-1000-OL photo
Loading ...
Loading ...
Loading ...
© 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com 14
NOTE: Each battery pack contains two battery connectors. The first battery pack is connected to the UPS using
the cable supplied with the pack. Each additional extension battery pack is connected by attaching its cable to
the previous pack. Refer to the figure below.
If additional battery packs (up to 4) are to be used, they should be connected prior to connecting the UPS to the
input power. To connect external battery packs, follow the steps below:
1. Set the circuit breaker to the “OFF” position.
2. Remove the battery connector cover from the UPS.
3. Remove the battery connector cover from the extended battery pack.
4. If there are multiple extended battery packs, remove the additional battery connector covers. If not, proceed
to Step 5.
5. Connect the supplied battery cable to the extended battery pack.
6. Connect the other end of the battery cable to the UPS.
7. For multiple extended battery packs, connect the supplied battery cables as shown in the figure below.
8. Set the circuit breaker to the “ON” position.
Loading ...
Loading ...