Emerson R652-DFF - Fisher LP-Gas Equipment Second Stage Regulator, Back Mount, 3/4" x 3/4" NPT, 9"-13" W.C. Spring

R600 and HSRL Series Instruction Manual - Page 2

For R652-DFF. Also, The document are for others Emerson models: R600 AND HSRL SERIES

PDF File Manual, 8 pages, Read Online | Download pdf file

R652-DFF photo
Loading ...
R600 and HSRL Series LP-Gas Regulators
2
Specifications
Pressure Taps Size Restriction
R600 Series: 1/8 in. NPT: #54 (0.055 in. / 1.40 mm)
Drill on outlet and inlet
HSRL Series: None
Orice Sizes
R600 Series (Except R632A and R632E Series):
7/32 in. / 5.6 mm
R632A and R632E Series: 0.256 in. / 6.5 mm
HSRL Series: 3/8 in. / 9.5 mm
Wide-open C
g
for Relief Sizing
R600 Series: 38
HSRL Series: 105
Maximum Allowable Inlet Pressure
(1)
Types R622H, R632A and R632E: 250 psig / 17.2 bar
Types R622E and R652E: 10 psig / 0.69 bar
Types R622, R642, R652 and HSRL Series:
10 psig / 0.69 bar
Maximum Emergency Inlet Pressure
(1)
Types R622H, R632A and R632E: 250 psig / 17.2 bar
Types R622E and R652E: 15 psig / 1.0 bar
Types R622 and R652: 50 psig / 3.4 bar
Type R642: 85 psig / 5.9 bar
Type HSRL: 30 psig / 2.1 bar
Temperature Capabilities
(1)
R600 and HSRL Series: -20 to 160ºF / -29 to 71ºC
(2)
Pressure Registration
Internal
Outlet Pressure Standard Setpoint
Types R622, R642, R652 and HSRL Series:
11 in. w.c. / 27 mbar
Type R632A:
First Stage: approximately 8 psig / 0.55 bar at
75 psig / 5.2 bar, 65 SCFH / 1.84 Sm
3
/h
Second Stage: 11 in. w.c. / 27 mbar
Outlet Pressure Standard Setpoint (continued)
Type R632E:
First Stage: approximately 8 psig / 0.55 bar at
75 psig / 5.2 bar, 65 SCFH / 1.84 Sm
3
/h
Second Stage: 2 psig / 0.14 bar
Types R622E and R652E: 2 psig / 0.14 bar
Type R622H: 10 psig / 0.69 bar, 5 psig / 0.34 bar
Outlet Pressure Spring Range
Types R622, R642 and R652:
7.5 to 9.5 in. w.c. / 19 to 24 mbar,
9 to 13 in. w.c. / 22 to 32 mbar,
13 to 20 in. w.c. / 32 to 50 mbar,
16 to 40 in. w.c. / 40 to 99 mbar
Type R632A:
First Stage: non-adjustable
Second Stage: 9 to 13 in. w.c. / 22 to 32 mbar
Type R632E:
First Stage: non-adjustable
Second Stage: 1 to 2.2 psig / 69 mbar to 0.15 bar
Types R622E and R652E:
1 to 2.2 psig / 69 mbar to 0.15 bar
Type R622H: 8 to 12 psig / 0.55 to 0.83 bar,
4 to 6 psig / 0.28 to 0.41 bar
HSRL Series: 9 to 13 in. w.c. / 22 to 32 mbar
Approximate Weight
Type R622H with POL Inlet:
1.7 lbs / 771 g
Types R632A and R632E with POL inlet:
2.9 lbs / 1310 g
Types R632A and R632E with NPT Inlet:
2.5 lbs / 1125 g
All Other R600 Series: 1.4 lbs / 635 g
HSRL Series: 4.5 lbs / 2.0 kg
Description
First Stage and 2 psig / 0.14 bar
Service Regulators
The Types R622H, R622E and R652E regulators are designed
for high pressure (pounds per square inch) vapor service. These
regulators have high capacity internal relief valves.
When used on first stage service, the Type R622H regulator
reduces container pressure to 10 psig / 0.69 bar for a second
stage regulator. On final stage service the regulator reduces
container pressure for a high pressure burner. The regulator is
normally painted RED.
The Type R622E or R652E standard outlet pressure setting is
2 psig / 0.14 bar. The regulator is painted PALM GREEN with a
WHITE CAP. It is an intermediate stage regulator that reduces
10 psig / 0.69 bar first stage pressure to 2 psig / 0.14 bar.
They are used on 2 psig / 0.14 bar pressure systems. The
Types R622E and R652E are not suitable for first stage service.
Second Stage Low Pressure Regulators
The Types R622, R642, R652 and HSRL Series regulators
provide low pressure (inches of water column) delivery
pressures. They are normally set at 11 in. w.c. / 27 mbar
pressure. They have high capacity internal relief valve
construction. The regulators are normally painted PALM
GREEN. The units differ in construction and capacity rating.
Specifications section, Tables 1 and 2 list the specifications for these regulators. Contact the factory if the regulator is to be
used on any service other than LP-Gas, natural gas or air. The following information is located on the spring case:
Type number, orifice size, spring range and date of manufacture.
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded.
2. Product has passed Fisher
®
testing for lockup, relief start-to-discharge and reseal down to -40ºF / -40ºC.
Loading ...
Loading ...
Loading ...