System Checkout
5
After the wiring and configuration is complete, built in automatic zone panel tests may be used to verify
equipment, damper, and panel operation.
To start the panel Test Mode:
1. Ensure all wiring is complete and power has been applied to the main and expansion panels
2. Press TEST for 3 seconds and release
3. Press SELECT to turn the test on and off
4. Press NEXT to move on to the next test
5. Press HOLD FOR EXIT for 3 seconds to exit test mode
The following tests are available in Test Mode:
Heating Stage(s) Test ON or OFF
This test turns on all heating stages (including O-B for heat pump
configurations) the system fan, and commands all dampers to
open. The heating stages will by energized by the type of system
configured in the installer settings. A heat pump configuration
will have all compressor calls and Auxiliary Heat. A conventional
configuration will call all conventional heating stages.
Press SELECT to Test or NEXT to advance to the next test.
Cooling Stage(s) Test ON or OFF
This test turns on the cooling stage (including O-B for heat pump
configurations), the system fan, and also commands all dampers
to open. Press SELECT to Test or NEXT to advance to the next test.
13