No. Installer Setting Display Factory Setting Comments
(Notes follow table) Indicator Default Options (More information follows this table)
10
Outdoor Sensor Compressor
COM BAL NO NO Disables Compressor Balance Point Control
Balance Point 0 to 50 Selects a Compressor Balance Point of 0 to 50° F
(-18˚C to 10˚C)
(-18˚ C to 10˚ C)
[Note 3, 4]
11 Outdoor Sensor Auxiliary AUX BAL NO NO, Disables Auxiliary Heat Balance Point Control
Heat Balance Point 40 to70 Selects an Auxiliary Heat Balance Point of 40 to 70° F
(4˚C to 22˚C)
(4˚ C to 22˚ C)
[Note 3, 4]
12 Equipment Staging STAGING ZON ZON Select to stage on number of zones calling (Setting 16)
TIM Select to stage on Zone Panel Timer
TST Select to stage on Thermostat Staging Calls [Note 5]
13 Upstage Time STAGTIM 10 5, 10, 15, Select an upstage timer of 5-30 minutes
20, 25, 30
14 Priority Zone PRIORTY OFF OFF Select to have opposite calls answered in any zone
1 or 2 Select zone 1 or 2 to limit calls so equipment will only
service call matching last call of zone 1 or 2.
15 Opposite Mode Timer OP MODE 15 15 to 60 Select the number of minutes to delay system changeover
when zones are calling for heat and others zones are
calling for cooling.
16 Zone to Activate EM HEAT 1 NO Select to disable Emergency Heat from Thermostats
Emergency Heat 1 or 2 Select which Zone on the main panel is allowed to
call for emergency heat. [Note 6]
12
NOTES - Configuration
[1] Set thermostats to conventional.
[2] O/B selection on equipment must match thermostat O/B selection.
[3] Only available if MSH system type is selected.
[4] Only available if outdoor sensor is connected.
[5] Multi-stage thermostats must be used.
[6] Thermostat type must be heat pump.