42
English
Installation Procedure
Installation Procedure
Outdoor-to-indoor power and communication
cables specifications
Indoor power supply
Power supply Max/Min (V) Indoor power cable
, 220-240V,
50/60 Hz
±10% 0.75 mm² ↑, 3 wires
Communication cable
0.75 mm², 2 wires
NOTE
Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord.
Code designation
[1-phase] IEC: 60245 IEC 57 / CENELEC: H05RN-F
grade or more
[3-phase] IEC: 60245 IEC 66 / CENELEC: H07RN-F
grade or more
When installing the indoor unit in a computer room
or net work room, use the double shielded (tape
aluminium / polyester braid + copper ) cable of
FROHH2R type.
CAUTION
Use rated cables or products only, with heat resistance
over 105°C, as well as properly rated switches or fuses
in the cabinet panel.
Make sure that the cables connected do not produce
sparks around the auxiliary power switch or that they
are not installed in a place subject to high temperature.
High ambient temperature decreases allowable
current.
Install the auxiliary power switch in a dry place, install
the panel board or electrical component box, and then
install the circuit breaker in the panel board.
When connecting the main power cable, press the cable
to the terminal for a secure connection.
Select a ring terminal for use.
R
B
2
Silver solder
d2
D
d1
B
F
E
L
Thickness of the wire
(mm²)
B (mm) d2 (mm)
2.5 Less than 9.5 More than 4.5
4 Less than 9.5 More than 4.5
6 Less than 9.5 More than 4.5
10 Less than 15 More than 8.4
Connecting the cable to the power terminal
Connect the cables to the terminal board with the ring
terminals.
NOTE
Be sure to use the certified and rated cables and firmly
connect them without applying any external force to
the ring terminal.
Connect with a driver and wrench that can apply the
rated torque to the screws.
Connect the terminal screws in compliance with the
rated tightening torques.
If the terminal is loose, a fire may occur, caused by
arcing electricity. If the terminal is connected too
firmly, the terminal may be damaged.