V-Tac VT-81010 COB PIR Sensor Two 360º Detection Rate

Product's Documents

Below are documents related to this product, you can read online or download:
VT-81010 photo

INSTRUCTION MANUAL

This is the main product document for model VT-81010.

The file format is pdf, 4 pages, you can download this manual here .

background
MODEL VT-81010
SKU 23426
INPUT VOLTAGE AC: 220-240V, 50/60 Hz
RATED LOAD
Max. 1200W
600W +LED
TIME DELAY
Min. 10sec ±3sec
Max. 15min ±2min
DETECTION
RANGE
360°
DETECTION
DISTANCE
8m Max (<24° C)
DETECTION
MOTION SPEED
0.6-1.5m/s
WORKING
TEMPERATURE
-20°C to +40°C
WORKING
HUMIDITY
<93%RH
POWER
CONSUMPTION
Approx, 0.9W
AMBIENT LIGHT <3-2000 LUX (Adjustable)
In case of any query/issue with the product, please reach out to us at: support@v-tac.eu
For More products range, inquiry please contact our distributor or nearest dealers.
V-TAC EUROPE LTD. Bulgaria, Plovdiv 4000, bul.L.Karavelow 9B
MULTI-LANGUAGE
MANUAL QR CODE
Please scan the QR code
to access the manual in
multiple languages.
INSTRUCTION MANUAL
INFRARED MOTION SENSOR
TECHNICAL DATA
INTRODUCTION & WARRANTY
Thank you for selecting and buying V-TAC product. V-TAC will serve you the best. Please read these instructions
carefully before starting the installation and keep this manual handy for future reference. If you have any another
query, please contact our dealer or local vendor from whom you have purchased the product. They are trained
and ready to serve you at the best. The warranty is valid for 5 years from the date of purchase. The warranty
does not apply to damage caused by incorrect installation or abnormal wear and tear. The company gives no
warranty against damage to any surface due to incorrect removal and installation of the product.
V-TAC LED
RANGE (UPTO 600W)
COMPATIBLE WITH
This marking indicates that this
product should not be disposed
of with other household wastes.
Caution, risk of electric shock.
IP RATING
IP20
INSTALLATION
HEIGHT
1.8-4m
CUTOUT SIZE
Ø63-66m
DIMENSION
Ø76x49 mm
background
FUNCTION
1. Can identify day and night: The consumer can adjust working state in dierent ambient light.
It can work in the daytime and at night when it is adjusted on the “sun” position (max). It can
work in the ambient light less than 3LUX when it is adjusted on the “3” position (min). As for the
adjustment pattern, please refer to the testing pattern.
2. Time-Delay is added continually: When it receives the second induction signals within the first
induction, it will restart to time from the moment.
As the detector responds to changes in temperature, avoid the following situations:
INSTALLATION ADVICE
Avoid pointing the detector towards objects with highly reflective surfaces, like mirrors etc.
Avoid mounting the detector near heat sources as heating vents, air conditioners, light etc.
Avoid pointing the detector towards objects that may move in the wind, such as curtains,
tall plants etc.
Good Sensitivity Poor Sensitivity
WARNING
1. Please make sure to turn o the power before starting the installation.
2. Installation must be performed by a qualified electrician.
3. Cover or shied any adjacent live components.
4. For indoor use only.
background
INSTALLATION
WIRING DIAGRAM
SENSOR INFORMATION
TEST
Turn the TIME knob anti-clockwise on the
minimum (10S). Turn the LUX knob clock-
wise on the maximum (sun).
Switch on the power; the sensor and its
connected lamp will have no signal at the
beginning. Aer Warm-up 30sec, the sen-
sor can start work. If the sensor receives the
Switch o the power.
Unload the transparent cover.
Connect the power to connection terminal of sensor according to connection-wire diagram.
Install back the transparent cover into the original location.
Fold the metal spring of the sensor upwards and then put the sensor into the suitable hole or
installation box. Releasing the spring, the sensor will be set in this installation position.
Aer finishing installing, turn on the power and then test it.
Height of Installation: 1.8-4m DETECTION DISTANCE: Max. 8m
background
The load does not work:
a. Please check if the connection of power source and load is correct.
b. Please check if the load is good.
c. Please check if the settings of working light correspond to ambient light.
The sensitivity is poor:
a. Please check if there is any hindrance in front of the detector to aect it to receive the signals.
b. Please check if the ambient temperature is too high.
c. Please check if the induction signal source is in the detection field.
d. Please check if the installation height corresponds to the height required in the instruction.
e. Please check if the moving orientation is correct.
The sensor can not shut o the load automatically:
a. Please check if there is continual signal in the detection field.
b. Please check if the time delay is set to the maximum position.
TROUBLESHOOTING
Note: when testing in daylight, please turn LUX knob to (SUN) position, Otherwise the
sensor lamp will not work.
induction signal, the lamp will turn on. While there is no another induction signal any more,
the load should stop working within 10sec±3sec and the lamp would turn o.
Turn LUX knob anti-clockwise on the minimum (3). If the ambient light is more than 3LUX, the
sensor would not work and the lamp stop working too. If the ambient light is less than 3LUX
(darkness), the sensor would work. Under no induction signal condition, the sensor should
stop working within 10sec±3sec.

Specifications