IR wireless remote
controller
Beeper sounds/
OPERATION
INDICATOR lamp
flashes
(Number of times)
Symptom
Re-
mark
Beeper sounds/
OPERATION
INDICATOR lamp flashes
(Number of times)
Check code
11 U9, UH Abnormality such as overvoltage or voltage shortage and abnormal and synchronous signal
to main circuit/Current sensor error
12
13
14 Others Other errors (Refer to the technical manual for the outdoor unit.)
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start sig-
nal was received and the OPERATION INDICATOR lamp does not come on, there are no error re-
cords.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the
initial two beeps to confirm the self-check start signal was received, the specified refrigerant ad-
dress is incorrect.
On IR wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
On wired remote controller
Check code displayed on the LCD
If the unit cannot be operated properly after the above test run has been performed, refer to the following
table to remove the cause.
Symptom
Cause
Wired remote controller LED 1, 2 (PCB in
outdoor unit)
PLEASE WAIT For about 2 minutes follow-
ing power-on
After LED 1, 2 are lighted, LED 2 is
turned off, then only LED 1 is ligh-
ted. (Correct operation)
For about 2 minutes after power-on, operation of the
remote controller is not possible due to system start-
up. (Correct operation)
PLEASE WAIT →
Error code
After about 2 minutes has
expired following power-on
Only LED 1 is lighted. → LED 1, 2
blink.
Connector for the outdoor unit’s protection device is
not connected.
Reverse or open phase wiring for the outdoor unit’s
power terminal block (L1, L2, L3)
Display messages do not
appear even when opera-
tion switch is turned ON
(operation lamp does not
light up).
Only LED 1 is lighted. → LED 1, 2
blinks twice, LED 2 blinks once.
Incorrect wiring between indoor and outdoor units (in-
correct polarity of S1, S2, S3)
Remote controller wire short
On the IR wireless remote controller with conditions above, following phenomena takes place.
No signals from the remote controller are accepted
OPE lamp is blinking
The buzzer makes a short ping sound
SVZ-KP12,18, 24, 30, 36NA
Specifications are subject to change without notice. 55 © 2022 Mitsubishi Electric US, Inc.