5/8”
(15mm)
PLASTIC TIE
PLASTIC TUBE
PLASTIC TIE
PLASTIC TUBE
CORRECT INCORRECT
Model Tube Length
SVZ-KP12/18/24 4.9 in. (125 mm)
SVZ-KP30/36 6.9 in. (175 mm)
DETAIL A
Reattach Bracket(s)
Electrical Knockouts
Side Drain Pan on bottom
Motor on bottom
Step. 11 Reinstall the coil assembly along with the bracket(s) that secure(s) it. Failure to reinstall the
brackets will result in capacity loss and condensation formation inside the cabinet. Be sure the ther-
mistor harness is reconnected inside the coil portion of the cabinet. Refer to 10.3 steps 1 to 4 to reas-
semble the panels. Ensure the proper knockouts are removed for drainage and electrical connections.
Thermistor
harness
Sharp edges
Drain
pan
CAUTION
When routing the
thermistor harness,
refer to the image to
the left to prevent
damage to the ther-
mistor harness by
avoiding any sharp
edges.
SVZ-KP12,18, 24, 30, 36NA