14.4. Changing blower external static pressure
The air handler is equipped with an adjustable static pressure setting. The available settings are shown in
the table below.
Model Available ESP [in. WG]
SVZ-KP12
0.30 0.50 0.80
SVZ-KP18
SVZ-KP24
SVZ-KP30
SVZ-KP36
The air handler will be set to 0.50 ESP from the factory.
The air handler’s static pressure can be changed through the mode/function settings in the controller.
Please refer to the installation manual for the controller on how to change this option. Depending on the
controller used, the mode/function will be either 08 for mode (PAR-31 & Simple MA) or 108 for function
(MHK1).
Vertical, Horizontal Left, Horizontal Right External Static Pressure Setting
External Static Pressure Setting No. of Mode/Function 08/108 Setting No. of Mode/Function 10/110 (Factory Setting)
0.3 in. WG [75Pa] 1 1
0.5 in. WG [125Pa]
(Factory Setting)
2 1
0.8 in. WG [200Pa] 3 1
SVZ-KP12,18, 24, 30, 36NA
© 2022 Mitsubishi Electric US, Inc. 48 Specifications are subject to change without notice.