PPrroodduucctt SSaaffeettyy
• To connect the UPS, instructions and operation described in the manual must be followed in the
indicated order.
• CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided with 20 or 30
amperes maximum branch circuit over current protection in accordance with the National Electric
Code.
• Check that the indications on the rating plate correspond to your AC powered system and to the
actual electrical consumption of all the equipment to be connected to the system.
• Ensure that the system is free of any contaminants, the surrounding area is free of debris, and
there are no foreign substances within the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Do not allow any liquids to enter the UPS. Do not place beverages or any other liquid-containing
vessels on or near the unit.
• This unit is intended for installation in a controlled environment (temperature-controlled, indoor
area free of conductive contaminants). Avoid installing the UPS in locations with standing or
running water or excessive humidity.
• Never install the system near liquids or in an excessively damp environment. This equipment
should only be used in a dry, indoor environment.
• Never let a foreign body penetrate inside the system.
• Do not plug the UPS input into its own output.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or to a heat source.
• Store the system in a dry place before installing, if storage is required.
• Unplug the UPS prior to cleaning, and do not use liquid or spray detergent.
• The admissible storage temperature range is -25ºC to +55ºC without batteries, 0°C to 40°C with
batteries.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection of
Information Technology Equipment, ANSI/NFPA.
• To reduce the risk of overheating the UPS, do not cover the unit’s cooling vents and avoid
exposing the UPS to direct sunlight or installing the unit near heat-emitting appliances such as
space heaters or furnaces.
SSppeecciiaall PPrreeccaauuttiioonnss
• The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling operations.
• All handling operations will require at least two people (unpacking, lifting, installation in rack
system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must
be energized for a period of 24 hours, at least once every 6 months (for a normal storage
temperature less than 25°C). This charges the battery, thus avoiding possible irreversible
damage.
• For potential safety issue on defective UPS : DISCONNECT INTERNAL BATTERY for storage and
transportation.