18 Eaton Tripp Lite SmartOnline Series User Guide 614-40204—Rev 01
Table 7. User Settings (Continued)
Main Menu Screen Submenu Submenu Menu Function
communication stays ON 90
minutes after the UPS is OFF.
SITE WIRING FLT ENABLED* (Default)
[ENABLED] [DISABLED]
Prevents the UPS from
starting in case of phase to
neutral wire swapping or
improper grounding,
BATTERY SETTINGS
AUTO BAT TEST MONTHLY*(Default) [NO
TEST] [DAILY] [WEEKLY]
[MONTHLY]
Allows the UPS to perform an
automatic battery test.
RESTART LEVEL 0%* (Default) [0%]....[100%] Allows the UPS to restart
when the set percentage
battery charge is reached.
BATT LOW LEVEL 0%* (Default) [0%]....[100%]
The alarm triggers when the
set percentage of battery
charge is reached.
BATT LOW TIME 3 MIN* (Default) [0MIN]
[3MIN] .. [60MIN]
The alarm triggers when the
set battery time remaining is
reached.
COM SETTINGS
REMOTE ON /OFF NO* (Default) [NO] [ROO]
[RPO] [BUILDING ALARM]
[FORCED BYPASS] [ON
GENERATOR] [SHUTDOWN
CMD]
Delay time and active cannot
set by LCD.
delay time: 3s
active: open
Sets events or faults that
actuate the output signal
through the external contact
connector or RS232
communications port.
REMOTE PWR OFF NO* (Default) [NO] [ROO]
[RPO] [BUILDING ALARM]
[FORCED BYPASS] [ON
GENERATOR] [SHUTDOWN
CMD]
Delay time and active cannot
set by LCD.
delay time: 3s
active: open
Sets events or faults that
actuate the output signal
through the external contact
connector or RS232
communications port.
INPUT DB9–4
NO* (Default) [NO] [ROO]
[RPO] [BUILDING ALARM]
[FORCED BYPASS] [ON
GENERATOR] [SHUTDOWN
CMD]
Delay time and active cannot
set by LCD.
delay time: 3s
active: open
Sets events or faults that
actuate the output signal
through the external contact
connector or RS232
communications port.
User Settings