28 Eaton Tripp Lite SmartOnline Series User Guide 614-40204—Rev 01
66..66 TTrraannssffeerrrriinngg BBeettwweeeenn MMooddeess
From Online (or Battery) to Bypass mode. Press any button to activate the menu options, then select
Control and go to Bypass.
From Bypass to Online (or Battery)mode. Press any button to activate the menu options, then select Control
and go to back Normal.
See 4.4 User Settings for help with navigation between settings.
66..77 SSeettttiinngg HHiigghh--EEffffiicciieennccyy mmooddee
In High-Efficiency mode, the UPS operates on bypass and transfers to Online (or Battery) mode in less than 10
ms when the utility fails. Transfers to High-Efficiency mode will be active after five minutes of bypass voltage
monitoring: if bypass quality is out of tolerance, then the UPS will remain in Online mode.
Eaton recommends using High-Efficiency mode only to protect IT equipment.
To set the High-Efficiency mode:
1. Select settings, In/Out settings, and High-Efficiency mode.
2. Select Enabled and press enter to confirm.
3. The UPS transfers to High-Efficiency mode after five minutes.
66..88 CCoonnffiigguurriinngg BBaatttteerryy SSeettttiinnggss
AAuuttoommaattiicc BBaatttteerryy TTeessttss
Automatic battery tests occur once a month in constant charging mode.
The battery test frequency can be modified.
During the test, the UPS transfers to Battery mode and discharges the batteries for ten seconds under load.
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below three minutes or less
than the setting capacity threshold (0% by default). This threshold can be modified.
Restart battery level
This setting is used to define the battery restart level. The battery level must reach this threshold (0% by
default) to enable the UPS to start.
See the 4.4 User Settings section to modify these settings.
66..99 RReettrriieevviinngg tthhee EEvveenntt LLoogg
To retrieve the event log through the display:
1. From the UPS home menu, press the
button to enter User Settings.
2. In the User Settings screen press the
or button until the Event Log menu is displayed.
3. Press the
button. Use the or buttons to display the events.
The log retains 50 events, with the most recent event listed first. Press the esc button twice to return to the
UPS home menu.
Transferring Between Modes