Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01 47
Table 18. Environmental and Safety (Continued)
cTUVus/NOM(TUV NOM)/Energy-star/CE (SU2200RTXL
SU3000RTXL Models)
cTUVus/Energy-star/CE/UKCA (SUINT1000LCD - SUINT3000LCD
Models)
CE/cTUVus- (BP36RT BP72RT Models)
Operating Temperatures
0 to 40 °C (32 to 104 °F) in Online mode, with linear derating
for altitude
Note: thermal protection switches load to Bypass in case of
overheating.
Protective class I
Output short-circuit current max RMS & delay time 68A/7 cycles; The max peak value: 92A
This UPS can be used in and supplied to load TN/TT/IT power system for HV models, TN power system for LV models.
UPS enclosure IP rating
IP20
Storage Temperatures
0 to 40°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
Transit Temperature
-25 to 55°C (-13 to 130°F)
Relative Humidity 0 to 96% no condensing
Operating Altitude
Up to 3,000 meters (9,843 ft) above sea level, no derating for
35°c (95°F) room temperature
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible Noise
< 50 dBA at 1 meter typical
Table 19. Battery
Internal Batteries EBM
Rack / Tower configuration
750VA: 36Vdc
1000VA LV: 36Vdc
1000VA INT: 48Vdc
1500VA: 48Vdc
2200VA: 72Vdc
3000VA: 72Vdc
BP36RT: 36Vdc- 2 x 3 x 12V. 9Ah
BP48RT: 48Vdc- 2 x 4 x 12V. 9Ah
BP72RT: 72Vdc- 2 x 6 x 12V. 9Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum 3-year float
service life at 25 °C (77 °F). Lifetime is reduced above 25°C (77°F)
EBM Battery Cable Length
350 mm / 13.78 in
Model Specifications