40 Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01
Table 10. UPS Alarm Codes (Continued)
Alarm Code
Displayed Alarm
Potential Cause Action
110 BUILDING ALARM
building alarm by input signal
contactor
 
200 BP PHASE NOT OK
Phase out of range (bypass
input and inverter output
cannot phase lock)
Check Bypass AC frequency
206 BP FREQ. NOT OK
Frequency out of range Check Bypass AC frequency
208 BP OVERLOAD
Bypass overload alarm
Check and reduce load
209 BP VOLT NOT OK
Input Voltage out of bypass
range
Please check input voltage
603 BATTERY MODE
Battery is discharging Please check input voltage
604 BATTERY LOW
Battery level is below
RemainingCapacityLimit
threshold or RunTimetoEmpty
is below RemainingTimeLimit
threshold.
Please check the mains and Prepare to
shut off load
60D NO BATTERY
Battery not present
Please check if batteries are connected
rightly or fuse is open
612 BAT TEST ABORTED
Battery test condition is not
met.
Check: UPS mode is AC (online) or HE;
Load must be greater than 10%;
Battery capacity should be >=80%;
There is no running alarm (excepted
Battery fault);
Load level has not varied by more than
+/- 10 percent (from the initial load level
present at the beginning of the test to
the beginning of step2 test).
700 CURRENT LIMIT inverter current limitation Check load
706 UPS TEMP. ALARM
UPS internal temperature is
high
Please check ambient temperature and if
the ventilation is blocked, and if fan
works normal.
802 IMMINENT SHUTOFF
shut down imminent for
battery low
Please prepare for shutdown
806 EMERGENCY OFF
emergency stop was proceed
Please check if RPO is active
80E OVLD PREALARM
output power above threshold
102%(default), settable from
HMI.
Check overload pre-alarm setting and
load
810 POWER OVERLOAD
Output power overload, Max
(P,S) > L2 (L2 = 102%)
Please check the load capacity
Typical Alarms and Faults