Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01 21
Table 7. User Settings (Continued)
Main Menu Screen Submenu Submenu Menu Function
IN / OUT SETTINGS
OUTPUT VOLTAGE 120V* (LV Default) [100V]
[110V] [120V] [125V]
208V* (HV Default) [200V]
[208V] [220V] [230V] [240V]
Sets the UPS output voltage,
UPS must be in standby to
choose output voltage setting.
OUTPUT FREQUENCY AUTOSENSING* (Default)
[AUTO SENSING] [FREQ
CONV. 50HZ] [FREQ CONV.
60HZ]
Sets the output frequency,
output frequency follows the
input frequency,
HIGH EFFIC. MODE DISABLED* (Default)
[ENABLED] [DISABLED]
Power the output from bypass
for high efficiency
OVERLOAD PREALARM 102%* (Default) [50%]
[55%]....[100%][102%]
Load % when overload alarm
occurs
ON / OFF SETTINGS
COLD START ENABLED* (Default)
[ENABLED] [DISABLED]
Allows the SmartOnline UPS
to start on battery power.
AUTO RESTART ENABLED* (Default)
[ENABLED] [DISABLED]
Allows the SmartOnline UPS
to restart automatically when
mains recovers after a
complete battery discharge.
AUTO START ENABLED* (Default)
[ENABLED] [DISABLED]
The SmartOnline UPS starts
up as soon as mains power is
available.
START ON BYPASS ENABLED* (Default)
[ENABLED] [DISABLED]
Allows the SmartOnline UPS
to start in bypass mode.
SLEEP MODE ENABLED* (Default)
[ENABLED] [DISABLED]
If Disabled, LCD and
communication will turn off
immediately afterSmartOnline
UPS is OFF. If Enabled, LCD
and communication stays ON
1h30 min after the
SmartOnline UPS is OFF.
SITE WIRING FLT ENABLED* (Default)
[ENABLED] [DISABLED]
Prevents the SmartOnline UPS
from starting in case of phase
to neutral wire swapping or
improper grounding,
BATTERY SETTINGS
AUTO BAT TEST MONTHLY*(Default) [NO
TEST] [DAILY] [WEEKLY]
[MONTHLY]
Allows the SmartOnline UPS
to perform an automatic
battery test.
RESTART LEVEL 0%* (Default) [0%]....[100%] Allows the SmartOnline UPS
to restart when the set
percentage battery charge is
reached.
BATT LOW LEVEL 0%* (Default) [0%]....[100%]
The alarm triggers when the
set percentage of battery
charge is reached.
User Settings