D.
E.
Condensate Tank & High Level Alarm - All KPAC II models come standard with
an internal condensate tank. The tank is equipped with an overflow safety cut-off. When
the tank is full, the safety will automatically shut down your unit, sound an audible alarm
and display a fault code (CF) this prevents accidental flooding of the conditioned space.
To continue operation when bottle is filled, see section II:B.
Service Ports - Located in the filter access compartment in the front of your KwiKool
below the control panel. This gives service personal a connection point for service
gauges to monitor the operating pressures of your KPAC II refrigeration system.
VI / Application Requirements
Air Temperature Requirements - The environmental requirements of your
KwiKool unit at the installation site are 60 to 110 degrees F for the condenser make-up
air located on the back of the unit. If the unit is operated in an environment above 110
F the high pressure switch may trip, stopping the unit’s compressor. You also may
notice diminished performance. The High Pressure Switch type is a manual reset. The
reset switch is located in the condenser make-up air inlet on the back of the system.
Reset the unit by pressing the button labeled HP Reset. Standard air-cooled KwiKool
models are not designed to operate at temperatures below 60 degrees F. Low-
ambient temperature controls must be special ordered at an additional cost.
Temperatures below 60 degrees F will cause freezing and or diminished performance
and can void your warranty.
Capacity & Temperature Settings - Sizing of our units is based on matching
capacity to a specific heat load while maintaining a 72 degree F temperature. In order
to reach temperatures below 72 degrees F, the unit must have extra capacity.
Positioning of Unit - Do not place your KwiKool unit in direct sunlight, the unit
should be positioned so that the output of the unit can be focused as close to the heat
generating equipment as possible with the front grill fully exposed. Do not block the
front of the unit, since this will cause a restriction in the airflow and can cause low
performance and/or evaporator coil freezing. The KPAC II will take condenser make-up
air from the area of placement and cannot be ducted, the inlet for the condenser
make-up air is located in the rear of the unit and will not allow for the back of the unit to
be placed flat against a wall or fixed object, not allowing at least 5 or 6 inches of space
between the inlet and a wall or fixed object will cause decreased performance and or
high pressure safety trip.
B.
A.
VII / Maintenance
Air Filters - Your KwiKool unit comes from the factory with filters installed on the
evaporator inlet to prevent dust and debris from entering the system and circulating in
the conditioned space, factory installed filters are a disposable type and must be
periodically checked and replaced based on the air quality of your conditioned space.
Failure to maintain the filters will cause restricted air flow and low overall unit
performance. The air filter is located on the front of your KwiKool unit below the
control, release the 2 slotted fasteners on the access door to open.