UMAT24HP230V1AC Gree Air Conditioner Cooling Area,

User Manual - Page 5

For UMAT24HP230V1AC.

PDF File Manual, 35 pages, Read Online | Download pdf file

UMAT24HP230V1AC photo
Loading ...
Loading ...
Loading ...
SYSTEM REQUIREMENTS
REFRIGERANT CHARGE
INDOOR UNIT ELECTRICAL REQUIREMENTS
PIPE SIZE in (mm)
Notes: Insulate both refrigerant lines, separately.
Communication Cable (Field Supplied):
Recommended cable - 18/2 AWG stranded bare copper
conductors THHN 300V unshielded wire Note: Use shielded cable if installation is in close proximity of RF
and EMI
transmitting devices.
Unit Size
(BtuH)
18,000 1/4 (6) 1/2 (12) 10 (3) 25(7.5)
164 (50)
49 (15)
24,000 3/8 (10) 5/8 (15) 10 (3) 25(7.5)
164 (50)
49 (15)
30,000 3/8 (10) 5/8 (15) 10 (3) 25(7.5)
164 (50)
49 (15)
36,000 3/8 (10) 5/8 (15) 10 (3) 25(7.5)
164 (50)
49 (15)
42,000 3/8 (10) 5/8 (15) 10 (3) 25(7.5)
164 (50) 49 (15)
48,000 3/8 (10) 5/8 (15) 10 (3) 25(7.5)
230(70) 49 (15)
Min Line
Max. Pre-Charge
Max Line
Max Elevation
Length
Line Length
Length
(ID over OD)
Liquid Suction/Gas
Line Line
Unit Size Refrigerant Factory System Additional
(BtuH) Type Charge oz (kg)* Charge oz/ft (g/m)
18,000 R410A 49.4 (1.4) 0.3 (30)
24,000 R410A 78.4 (2.2) 0.6 (60)
30,000 R410A 84.6 (2.4) 0.6 (60)
36,000 R410A 123.2 (3.6) 0.6 (60)
42,000 R410A 131.2 (3.8) 0.6 (60)
48,000 R410A 141.8 (4.1) 0.6 (60)
Unit Size
Voltage
Min Circuit Max Overcurrent Main Power
(BtuH) Amps (MCA) Protection (MOCP) Wire Size (AWG)
18,000 208/230v - 1ph 60hz 1.0 15 14
24,000 208/230v - 1ph 60hz 1.0 15 14
30,000 208/230v - 1ph 60hz 1.5 15 14
36,000 208/230v - 1ph 60hz 1.5 15 14
42,000 208/230v - 1ph 60hz 1.5 15 14
48,000 208/230v - 1ph 60hz 2.0 15 14
OUTDOOR UNIT ELECTRICAL REQUIREMENTS
Unit Size
Voltage
Min Circuit Max Overcurrent Main Power
(BtuH) Amps (MCA) Protection (MOCP) Wire Size (AWG)
18,000 208/230v - 1ph 60hz 17.0 25 10
24,000 208/230v - 1ph 60hz 24.0 40 10
30,000 208/230v - 1ph 60hz 24.0 40 10
36,000 208/230v - 1ph 60hz 29.0 45 8
42,000 208/230v - 1ph 60hz 31.0 50 8
48,000 208/230v - 1ph 60hz 45.0 70 6
*Precharge amount for up to 25-ft of refrigerant pipe.
REFRIGERANT LINE LENGTHS ft (m)