Specifications
Model OMNIVS800LCD OMNIVS1000LCD OMNIVS1200LCD OMNISMART
700TSU
OMNIVS1500LCD
Nominal input
voltage(s) and range:
120V~, 89-145V~ 120V~, 89-145V~ 120V~, 89-145V~ 120V~, 89-145V~
120V~, 89-145V~
Nominal input
frequency and
tolerance:
50/60 Hz
(+/- 5 Hz)
50/60 Hz
(+/- 5 Hz)
50/60 Hz
(+/- 5 Hz)
50/60 Hz
(+/- 5 Hz)
50/60 Hz
(+/- 5 Hz)
Nominal output
voltage:
120V~ sinusoidal
in line mode and
120V~ PWM in
battery mode
120V~ sinusoidal
in line mode and
120V~ PWM in
battery mode
120V~ sinusoidal
in line mode and
120V~ PWM in
battery mode
120V~ sinusoidal
in line mode and
120V~ PWM in
battery mode
120V~ sinusoidal
in line mode and
120V~ PWM in
battery mode
Nominal output
frequency:
50/60 Hz
(+/-0.5 Hz)
50/60 Hz
(+/-0.5 Hz)
50/60 Hz
(+/-0.5 Hz)
50/60 Hz
(+/-0.5 Hz)
50/60 Hz
(+/-0.5 Hz)
Output voltage
regulation in line
mode:
120 V~
(+6% / - 12%)
120 V~
(+6% / - 12%)
120 V~
(+6% / - 12%)
120 V~
(+6% / - 12%)
120 V~
(+6% / - 12%)
Output voltage
regulation in
battery mode:
120V~ (+/-10%) 120V~ (+/-10%) 120V~ (+/-10%) 120V~ (+/-10%) 120V~ (+/-10%)
Nominal output
power in W / VA:
475W / 800VA 560W / 1000VA 600W / 1200VA 480W / 700VA 900W / 1440VA
Output voltage
waveform:
Sinusoidal in
line mode and
quasi-sine (PWM)
in battery mode
Sinusoidal in
line mode and
quasi-sine (PWM)
in battery mode
Sinusoidal in
line mode and
quasi-sine (PWM)
in battery mode
Sinusoidal in
line mode and
quasi-sine (PWM)
in battery mode
Sinusoidal in
line mode and
quasi-sine (PWM)
in battery mode
Maximum output
current @ P.F.
6.7A @ 120V~ 8.3A @ 120V~ 10A @ 120V~ 5.8A @ 120V~ 12A @ 120V~
P.F. = 0.6 P.F. = 0.56 P.F. = 0.5 P.F. = 0.685 P.F. = 0.625
Efficiency with
nominal load:
95% 95% 95% 95% 95%
Maximum
operating altitude
at 100% of
nominal power:
2,000 m above
the sea level
2,000 m above
the sea level
2,000 m above
the sea level
2,000 m above
the sea level
2,000 m above
the sea level
Online overload
capability:
110%±10%, goes
to fault after 5
min.; 120%±10%,
goes to fault
immediately
110%±10%, goes
to fault after 5
min.; 120%±10%,
goes to fault
immediately
110%±10%, goes
to fault after 5
min.; 120%±10%,
goes to fault
immediately
110%±10%, goes
to fault after 5
min.; 120%±10%,
goes to fault
immediately
110%±10%, goes
to fault after 5
min.; 120%±10%,
goes to fault
immediately
Overload capacity
in battery mode:
110%±10% shuts
down in 5 sec.;
120%±10%,
shuts down
immediately
110%±10% shuts
down in 5 sec.;
120%±10%,
shuts down
immediately
110%±10% shuts
down in 5 sec.;
120%±10%,
shuts down
immediately
110%±10% shuts
down in 5 sec.;
120%±10%,
shuts down
immediately
110%±10% shuts
down in 5 sec.;
120%±10%,
shuts down
immediately
Current limitation: Input 10A Input 15A Input 15A Input 10A Input 15A
Autonomy time
at full load:
3 minutes @
475W
2 minutes @
560W
2 minutes @
600W
3 minutes @
480W
2 minutes @
900W
Battery recharge
time:
8 hours 8 hours 8 hours 8 hours 8 hours
Transfer time: 6 milliseconds
typical (10 milli-
seconds max)
6 milliseconds
typical (10 milli-
seconds max)
6 milliseconds
typical (10 milli-
seconds max)
6 milliseconds
typical (10 milli-
seconds max)
6 milliseconds
typical (10 milli-
seconds max)
Outlets: 6x 5-15R outlets
with battery back-
up, regulation and
surge, 2x 5-15R
outlets only for
surges
6x 5-15R outlets
with battery back-
up, regulation and
surge, 2x 5-15R
outlets only for
surges
6x 5-15R outlets
with battery back-
up, regulation and
surge, 2x 5-15R
outlets only for
surges
6x 5-15R outlets
with battery back-
up, regulation and
surge, 2x 5-15R
outlets only for
surges
6x 5-15R outlets
with battery back-
up, regulation and
surge, 2x 5-15R
outlets only for
surges
Maximum input
current:
10A 12A 12A 10A 15A
21-10-017-9338D9-Book.indb 1221-10-017-9338D9-Book.indb 12 10/15/2021 2:45:54 PM10/15/2021 2:45:54 PM