TP-7092 2/2164 Section 4 Scheduled Maintenance
d. Reconnect the generator set engine starting
battery, negative (- ) lead last.
e. Reconnect the utility power to the generator
set.
f. Press the RUN button on the generator set
controller. The generator set will start.
g. Run the generator set for a minute to allow the
oil pressure to reach operating range.
h. Stop the generator set, wait 1 minute, and then
recheck the oil level. Add oil to bring the level
up to the F mark on the dipstick.
4. Check for leaks.
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the housing side panel.
5. Reset the maintenance timer on the controller.
4.2.5 Resetting the Maintenance Timer
1. From the Overview menu, step down to the Genset
Run Time menu.
2. Press the Select button and then step down to the
Next Maintenance screen.
3. Press the Select button.
4. Press the Up arrow button so that “Reset Maint
Timer? Yes” is displayed.
5. Press the Select button. After about two
minutes, the new maintenance interval and date
are displayed.
4.2.6 Oil Cooler (20RCA/RCAL only)
Inspect and clean the oil cooler at the intervals indicated
in the service schedule. The oil cooler must be kept free
of debris.
See Figure 4-3 and Figure 4-4 for the oil cooler location.
The oil cooler is located under the No. 2 cylinder shroud.
Remove the top mounting screw and loosen the two side
screws, then lift off the cylinder shroud.
Clean the outside of the oil cooler fins with a brush or
with compressed air.
1
62 590 01
Note: See Figure 4-3 for location.
1. Oil cooler
Figure 4-4 Oil Cooler