Your AprilAire Digital Humidier Control is installed in the cold air
return duct. During the rst heating season, your humidier control
needs to be set initially to match your home’s condition. Please follow
these steps when adjusting your control (refer to FIGURE A).
1. Turn the dial setting knob to 5, which is within the normal range.
During the next 24-48 hours it may be necessary to adjust the dial
for more or less humidity, depending on your personal comfort
and home’s requirements. Refer to TABLE 3: Operation Guide.
2. During the coldest portion of the rst heating season, minor
adjustments may be necessary. This is dependent upon your
home’s construction. Refer to TABLE 3: Operation Guide.
The RH in your home will now be accurately controlled to meet your
needs and should not need further adjustment during future heating
seasons. Make note of the dial setting in the event you temporarily
move the knob to OFF when performing annual maintenance of your
AprilAire Humidier.
90-1235
FIGURE A: ADHC (AUTOMATIC MODE)
AUTOMATIC MODE
Once blower activation mode is initiated, the humidier and
HVAC system fan will continue to operate for 2 hours or until the
humidication set point is reached.
When the BLOWER ACTIVATION switch is in the OFF position, the
humidier control will only operate the humidier if the HVAC system
fan or heat is on AND if the RH is lower than the set point.
7