Howard McCray SF22-S-FF Howard-McCray 26.50'' 22.0 cu. ft. Top Mounted 1 Section Solid Door Reach-In Freezer

Owner s manual - Page 23

For SF22-S-FF.

PDF File Manual, 26 pages, Read Online | Download pdf file

SF22-S-FF photo
Loading ...
Loading ...
Loading ...
10:53 AM FREEZER-SOLID DOOR -5F(-21C) 11/18/2011
Label Name Set-F Set-C Label Name Set-F Set-C
Set Set Point -5 -21 FSt Fan stop temperature 20 -7
HY Differential 5 3 Fon Fan on time with compressor off 0 0
LS Min Set Point -20 -29 FOF Fan off time with compressor off 0 0
US Max. Set Point 10 -12 FAP Fan sensor probe P2 P2
ot Thermo Probe Calibration 0 0 ALC Temp. alarm configuration Ab Ab
P2P Evap. Probe Presence Y Y ALU MAX. temperature alarm 15 -9
oE Evap. Probe Calibration 0 0 ALL MIN. temperature alarm -25 -32
P3P Third Probe Presence n n AFH Diff for temp. alarm recovery 2 2
o3 Third Probe Calibration 0 0 ALd Temp. alarm delay 60 60
P4P Fourth Probe Presence n n dAo Delay of temp alarm at start up 2.0 2.0
o4 Fourth Probe Calibration 0 0 AP2 Probe for temp. alarm of cond P4 P4
odS Output Delay - Start Up 1 1 AL2 Cond for low temp alarm -40 -40
AC Anti-Short Cycle Delay 1 1 AU2 Cond for high temp alarm 230 110
rtr P1-P2 Percentage 100 100 AH2 Diff for cond. Temp alarm rec 4 4
CCt Continuous Cycle Duration 0 0 Ad2 Cond temp alarm delay 15 15
CCS Set Point - Continuous Cycle 0 0 dA2 Delay of cond temp alarm start up 1.3 1.3
Con Comp. ON - Faulty Probe 18 18 bLL Comp off for cond low temp alarm n n
CoF Comp. OFF - Faulty Probe 12 12 AC2 Comp off for cond high temp alarm n n
CF Temp. Measure Unit F C i1P Digital input polarity CL CL
rES Resolution in in i1F Digital input configuation EAL EAL
Lod Probe Display P1 P1 did Digital input alarm delay 5 5
dLy Display Temp Delay 0 0 Nps Number of act of pressure switch 15 15
dtr P1-P2 Percentage for Display 50 50 odc Compress status when open dr no no
tdF Defrost Type EL EL rrd Regulation restart with DR open alarm y y
dFP Probe Selection Defrost Term P2 P2 HES Differential for energy saving 0 0
dtE Defrost Term Temp. 50 10 Adr Serial address 1 1
idF Interval Between Defrost Cycle 8 8 PbC Kind of probe NTC NTC
NdF Max. Length for Defrost time 30 30 onF on/off key enabling no no
dSd Start defrost delay 0 0 dP1 Room probe display -- --
dFd Displaying during defrost rt rt dP2 Evaporator probe display -- --
dAd MAX display delay after def. 0 0 dP3 Third probe display noP noP
Fdt Draining time 1 1 dP4 Fourth probe display noP noP
dPo First defrost after startup n n rSE Value of Set Point -- --
dAF Defrost delay after fast freez 0.0 0.0 rEL Software release 1.0 1.0
FnC Fan operating mode O-n O-n Ptb Map code 10 10
Fnd Fan delay after defrost 2 2 BOLD Pr2
FCt Differential of temperature for forced activati
o
0 0 BOLD = PARAMETER 2
SENSING @ TEV OUTLET
TO SEE SET POINT TEMPERATURE, PRESS SET KEY AND RELEASE TO DISPLAY SET POINT
Dixell Control Factory (F-C) Settings July 12, 2011 XR60CX- (20-478)
1 of 1 XR60CX Freezers (F-C) Setting 110712.xls