Optional Installation continued
3
External Battery Connection
(Select Models)
YourUPScomeswitharobustinternal
batterysystem;externalbatteriesare
neededonlytoextendruntime.Adding
externalbatterieswillincreaserechargetime
aswellasruntime.ThisUPSsupports
BP36V15-2U(limit1)andBP36V42-3U
(unlimited).
The illustration (see
3
)showsthelocationofyourUPS’sExternalBatteryConnector
A
where
you will insert the battery pack cable. Complete installation instructions for your battery pack
appearinthebatterypackowner’smanual.Makesurethatcablesarefullyinsertedintotheir
connectors.Smallsparksmayresultduringbatteryconnection;thisisnormal.
DonotconnectordisconnectbatterypackswhentheUPSisrunningonbatterypower.
CAUTION! When an external battery pack is connected, make sure the AC load does not
exceed the nameplate rating. Select models are derated when an external battery pack
is connected. See UPS nameplate label for derating details.
WhenconnectingexternalbatteriestotheUPS,gototheTrippLitewebsiteatwww.tripplite.com/
en/support/bpconfig/index.cfmtodownloadtheExternalBatteryPackUtilitysoftwaretoconfigure
yourUPSforexternalbatterysupport.
Model Name
Wattage with Internal
Batteries Only
Wattage with External
Batteries Attached
SMART1500RMXL2UA1350W1200W
SMART1500RM2U1350WN/A
SMART1000RMXL2U900W800W
Note:
1. The runtime will automatically recalculate once the External Battery Pack Tool process is complete.
2. If the setup will no longer include external batteries, the UPS can be configured to work without external
batteries via the LCD Screen. See External Battery Settings Control section under Basic Operation for details.
3. If external battery packs are removed, the UPS must be reset to “NO EXTERNAL BATTERY” via the LCD
interface or the External Battery Configuration Program available on the Tripp Lite website. Failure to do so
may result in damage to the internal batteries due to over-charging.