Tripp Lite S3M30KX SmartOnline S3MX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS

Owner's Manual - Page 49

For S3M30KX. Also, The document are for others Tripp Lite models: S3M30KX-NIB, S3M40KX, S3M40KX-NIB, S3M60KX, S3M80KX

PDF File Manual, 260 pages, Read Online | Download pdf file

S3M30KX photo
Loading ...
Loading ...
Loading ...
49
8. Specifications
MODELS S3M30KX S3M40KX S3M60KX S3M80KX
Capacity (VA) 30 kVA 40 kVA 60 kVA 80 kVA
Capacity (Watts) 27 kW 36 kW 54 kW 72 kW
INPUT
Nominal Voltage Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
Voltage Range
Ph-Ph 208-478V at < 50% Load; Ph-Ph 208-478V to 305-478V at 50% to 80% Load
(Voltage Range Varies with Load); Ph-Ph 305-478V at > 80% Load
Voltage Comeback Low-Loss Voltage +10V; High-Loss Voltage -10V
Nominal Frequency 50/60 Hz (Auto-Selectable)
Frequency Range 46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System)
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Power Factor (100% Load) 0,99
Harmonic Distortion (THDi; 100% Load) < 3%
OUTPUT
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Nominal Voltage Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
AC Voltage Regulation
(Double-Conversion Mode)
±1% (Balanced Load)
AC Voltage Regulation
(Converter Mode or Battery Mode)
±1%
Power Factor 0,9
AC Voltage Regulation (ECO Mode) ± 11V of Nominal
Frequency 46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System)
Frequency Regulation
(Converter Mode or Battery Mode)
± 0,1 Hz
Frequency Range (Battery Mode) 50 Hz ± 0,1 Hz or 60 Hz ± 0,1 Hz
Overload (AC Mode) Up to 110% = 10 min; Up to 130% = 1 min; > 130% = 1 s
Overload (Battery Mode) Up to 110% = 30 s; Up to 130% = 10 s; > 130% = 1 s
Current Crest Ratio 3:1 Maximum
Harmonic Distortion (100% Load) 2% THD (Linear Load); 4% THD (Non-Linear Load)
Transfer Time (Line ‹—› Battery) 0 ms
Transfer Time (Inverter ‹—› Bypass) Synchronous = 0 ms; Asynchronous < 4 ms
Transfer Time (Inverter ‹—› ECO) < 10 ms
BYPASS INPUT
Nominal Voltage Ph-Ph 380V/400V/415V
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Voltage Range
Upper Limit: Ph-N 231-264V
Lower Limit: Ph-N 176-209V
Nominal Frequency 50/60 Hz (Auto-Selectable)
Frequency Range Selectable: ± 1-4 Hz (Default: ± 4 Hz)
Overload (Bypass Mode) < 150% = 1 min
EFFICIENCY
AC Line Mode 94% at 100% Resistive Load; 93,5% at 50% Resistive Load
ECO Mode 98%, at 100% Resistive Load; 97,5% at 50% Resistive Load
Battery Mode 93,5% at 100% Resistive Load; 93% at 50% Resistive Load
PARALLEL
Parallel for Capacity Up to 3 Units
Parallel for Redundancy N/A
INTERNAL BATTERIES (S3M30KX and S3M40KX include internal batteries. Versions are also available without internal
batteries installed: S3M30KX-NIB and S3M40KX-NIB.)
Type 12V Non-Spillable VRLA AGM/GEL
No Internal Batteries
External Batteries Required for
S3M30KX-NIB, S3M40KX-NIB,
S3M60KX, S3M80KX, S3M100KX,
S3M120KX, S3M160KX and S3M200KX
Capacity 9 Ah 10 Ah
Quantity 80 (2 x Strings of 20 + 20)
Runtime (50% / 100% Load) 17/5.7 min 15/5 min
Recharge Time 9 h to 90%
Maximum Charging Current 2A ± 10%
Float Voltage 13,65V/Battery; 2,27V/Cell
Boost Charging 14,1V/Battery; 2,35V/Cell
End of Discharge 10V/Battery; 1,67V/Cell