Tripp Lite S3M30KX SmartOnline S3MX Series 3-Phase 380/400/415V 30kVA 27kW On-Line Double-Conversion UPS

Owner's Manual - Page 33

For S3M30KX. Also, The document are for others Tripp Lite models: S3M30KX-NIB, S3M40KX, S3M40KX-NIB, S3M60KX, S3M80KX

PDF File Manual, 260 pages, Read Online | Download pdf file

S3M30KX photo
Loading ...
Loading ...
Loading ...
33
4. Operation
Programs Available List for Parameter 1:
Code Description
Bypass /
No Output mode
AC
Mode
ECO
Mode
CVCF
Mode
Battery
Mode
Battery
Test
01 Output voltage Y*
02 Output frequency Y
03 Voltage range for bypass Y
04 Frequency range for bypass Y
05 ECO Mode enable/disable Y
06 Voltage range for ECO Mode Y
07 Frequency range for ECO Mode Y
08 Bypass Mode setting Y Y
09 Maximum battery discharge time setting Y Y Y Y Y Y
10 Reserved Reserved for future options
11 Hot standby function setting Y
12 Neutral loss detection Y Y Y Y Y Y
13 Battery voltage calibration Y Y Y Y Y Y
14 Charger voltage adjustment Y Y Y Y Y Y
15 Inverter A voltage adjustment Y Y Y
16 Inverter B voltage adjustment Y Y Y
17 Inverter C voltage adjustment Y Y Y
18 Output A voltage calibration Y Y Y
19 Output B voltage calibration Y Y Y
20 Output C voltage calibration Y Y Y
21 Charger current setting Y
22 Charging boards quantity setting Y
*Y means that this program can be set in this mode.
Note: All parameter settings will be saved only when the UPS shuts down normally with an internal or external battery connection. Normal UPS shutdown
means turning off input breaker in Bypass/No Output Mode.
01: Output Voltage
Interface Setting
Parameter 3: Output voltage
For 220/230/240V AC models, you may choose the following output voltage:
220: Output voltage is 220V AC.
230: Output voltage is 230V AC (Default).
240: Output voltage is 240V AC.