Troubleshooting SiUS091133
141 Service Diagnosis
Troubleshooting
Check No.15
Refer to P.146
Check No.17
Refer to P.149
Check No.18
Refer to P.150
Check No.22
Refer to P.153
(R15830)
Caution
NO
YES
NO
YES
NO
YES
YES
NO
NO
YES
YES
NO
An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Check No. 18
Check the discharge pressure.
Check No. 22
Check the power module.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter checker ().
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Turn off the power and turn it on
again to start the system. See if the
same error occurs.
Check the power supply voltage.
Monitor the power supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
Momentary fall of power supply
voltage
Compressor overload
Short circuit
Keep on using.
Check the connectors and
other components.
Fully open the stop valve.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Error again?
Stop valve fully open?
Voltage as rated?
Any LED off?
Normal?
Inverter checker
Part No.: 1225477
Short circuit or
wire breakage between
compressor's coil
phases?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.