4 Eaton Tripp Lite Series SUPDMBP6K User Guide 934705—Rev A
22..33 DDeessccrriippttiioonn // PPaanneellss
The SUPDMBP6K has a manual rotary bypass switch with two positions:
UPS: the load is supplied by the UPS.
Bypass: the load is supplied directly by the AC source.
Two lights that indicate the SUPDMBP6K power status:
“UPS” green LED: when active, the UPS output is available, the bypass switch can be safely turned to the
UPS position.
“BYPASS” red LED: when active, indicates that the SUPDMBP6K is on "Bypass mode" (The bypass
switch is turned to the bypass position).
UPS input switch
Switches off the AC source to the UPS for maintenance or replacement.
SUPDMBP6K status detection:
A signal cable, with RJ11 connector to plug to the UPS, allows the communication to the UPS to manage the
SUPDMBP6K status, and the indication on UPS display panel of both following status:
SUPDMBP6K connection to UPS.
Manual bypass switch position.
Check the Smartonline UPS User's Manual to check the compatibility of this feature, or contact Tripp Lite for
more information.
Figure 2. SUPDMBP6K
Input / Output terminal blocks
UPS input switch
Input / Output detection connector to
UPS
Manual bypass switch
(2) L6-30 locking receptacle cords
(2) L6-20 locking receptacle cords
“Bypass” mode red LED
UPS mode green LED
1
2
3
5
6
7
8
4
1
2
3
4
5
6
7
8
9
9
20A double pole 250V breaker
ON
ON
OFF
OFF
BYPASS
UPS
UPS INPUT SWITCH
NORMAL AC SOURCE
OUTPUT
20 AMP
Description / Panels