Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01 43
Table 17. Electrical output (Continued)
Nominal output
100 / 110 / 120 / 125 (for 120V models)
Frequency 50 or 60Hz. autosensing or configurable as a frequency converter
Output overload
(Online Mode)
102%~130%* 12 seconds
130%~150%* 2 seconds
>150%*
Shutdown immediately**
Output overload
(Battery Mode)
102%~130%* 12 seconds
130%~150%* 2 seconds
>150%*
Shutdown immediately, overload warning **
Output overload
(Bypass Mode)
102%~110%*
Overload warning
110%~130%* Shutdown after 5 minutes
130%~150%* Shutdown after 15 seconds
>150%* Shutdown after 300 ms
Voltage waveform
Sine wave
Harmonic distortion
< 3% THDV on linear load
< 5% THDV on non-linear load
Transfer time
Online mode: 0 ms
High Efficiency mode: 10 ms maximum (due to loss of utility)
Power factor
Up to 0.9
Load crest ratio
Up to 3:1
* Percent is based on nominal Watt/VA
** Behaviour can change (see output mode in In/Out settings)
Table 18. Electrical Output Connections
Catalog Number (UPS)
Output Connection Output Cable
SU700XLCD
(2) NEMA 5–15R
(2) NEMA 5–15R Group1
(2) NEMA 5–15R Group2
NASU1000XLCD
SU1500XLCD
SU2200XLCD
(2) NEMA 5–20R Primary
(2) NEMA 5–20R + (1) NEMA L5–20R
Group 1
(2) NEMA 5–20R Group2
NA
SU3000XLCD
(1) NEMA L5–30R Primary
(2) NEMA 5–20R Group1
(2) NEMA 5–20R Group2
Model Specifications