16 Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01
Table 6. Display Functions (Continued)
Main Menu Submenu
Display Information or Menu function
EVENT LOG
Event log has 50 items to show what
happened.
IDENTIFICATION
This menu shows IDENTIFICATION
information.
44..55 UUsseerr SSeettttiinnggss
The following table displays the options that can be changed by the user. From the UPS Home Menu press the
button. This will open the Main Menu Screen . To select a menu option use the or buttons. Press the
button to validate the selected item. Pressing the ESC button will exit to the previous menu level / screen.
Table 7. User Settings
Main Menu Screen Submenu Submenu Menu Function
CONTROL
GO TO BYPASS / GO BACK
NORMAL
GO TO BYPASS / GO BACK
NORMAL?
GO TO BYPASS command is
used to force ups to bypass
mode from ONLINE MODE.
GO BACK NORMAL command
is used to comeback to line
mode from BYPASS MODE.
BATTERY TEST BATTERY TEST? BATTERY TEST command is
used to start battery test.
RESET FAULT ST RESET FAULT ST? RESET FAULT ST command is
used to reset all faults. But
some faults may not be
cleared.
CLEAR EVENT LOG CLEAR EVENT LOG? CLEAR EVENT LOG command
is used to clear all the event
log.
RESET KWH USED RESET KWH USED? RESET KWH USED is used to
reset the power used.
FACTORY SETT FACTORY SETT? FACTORY SETT command is
used to restore factory
settings.
LOCAL SETTINGS
LANGUAGE ENGLISH* (Default)
[FRANCAIS] [ESPANOL]
Sets displayed language for
Menus, status and alarms.
UPS fault, Event log data and
settings are in all supported
languages.
AUDIBLE ALARM
ENABLED* (Default)
[ENABLED] [DISABLED ON
BAT] [ALWAYS DISABLED]
Enables or disables the
audible alarm.
IN / OUT SETTINGS
OUTPUT VOLTAGE 120V* (LV Default) [100V]
[110V] [120V] [125V]
208V* (HV Default) [200V]
[208V] [220V] [230V] [240V]
Sets the UPS output voltage,
UPS must be in standby to
choose output voltage setting.
User Settings