Tripp Lite BP48V NEW series 48V Extended Battery Module EBM

Eaton Tripp Lite SmartOnline Series Tower UPS Advanced User Guide - Page 31

For BP48V NEW.

PDF File Manual, 52 pages, Read Online | Download pdf file

BP48V NEW photo
Loading ...
Loading ...
Loading ...
Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01 25
CChhaapptteerr 55 OOppeerraattiioonn
55..11 SSttaarrtt--uupp aanndd NNoorrmmaall ooppeerraattiioonn
To start the UPS:
1. Verify that the internal batteries are connected. See
3.3 SmartOnline UPS Installation.
2. If optional EBMs are installed, verify that the EBM are connected to the UPS. See section
3.3 SmartOnline UPS Installation.
3. Verify that the UPS power cord is plugged in.
4. The UPS front panel display illuminates and displays the UPS Home Menu see
4.3 UPS Home Menu.
5. Press the
button on the UPS front panel for at least 2 seconds. The UPS display will read “UPS
Starting” .
6. Check the UPS front panel display for active alarms or notices. If the
indicator is on, do not proceed
until all alarms are cleared. Check the UPS status from the front panel to view the active alarms. Correct
the alarms and restart if necessary. See
7.1 Typical Alarms and Faults .
7. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected. The UPS should be in normal mode.
55..22 SSttaarrttiinngg tthhee UUPPSS oonn BBaatttteerryy
NOTE By default the “Cold Start or battery start setting is enabled from the factory.
To start the UPS on battery:
1. Press the
button on the UPS front panel until the UPS front panel display illuminates and shows a
status of "UPS Starting...". The UPS transfers from Standby mode to Battery mode. The
indicator
illuminates solid. The UPS supplies power to your equipment.
2. Check the UPS front panel display for active alarms . Resolve any active alarms before continuing. See the
"
7.1 Typical Alarms and Faults " section .
55..33 UUPPSS SShhuuttddoowwnn
To shut down the UPS:
1. Press the
button on the front panel for three seconds. The UPS then transfers to Standby mode and
the
indicator turns off. If utility power is removed from the input of the UPS while in the “Standby
Mode” the system will then begin to shut down after 10 seconds.
55..44 OOppeerraattiinngg mmooddeess
The Tripp Lite by Eaton SmartOnline UPS front panel indicates the status through the front panel indicators,
See section
4.1 Control Panel.
Online Mode
During Online mode, the indicator illuminates solid and the UPS is powered from the utility. The UPS
monitors and charges the batteries as needed and provides filtered power protection to your equipment.
Optional High Efficiency and Energy Saving settings minimize heat contribution to the rack environment. See
section
4.5 User Settings.
Loading ...
Loading ...
Loading ...