30
8. Specifications
MODEL SVT10KX SVT20KX SVT30KX
CAPACITY 10000VA / 9000W 20000VA / 18000W 30000VA / 27000W
TOPOLOGY Voltage and Frequency Independent (VFI) Double Conversion
INPUT
Voltage Range 220/230/240V(Ph-N),380/400/415V(Ph-Ph)
Frequency Range 46 Hz ~ 54 Hz @ 50 Hz system
56 Hz ~ 64 Hz @ 60 Hz system
Phase Three phase with Neutral
Power Factor
0.99 at 100% Load
Input THD <6%
Input Voltage Tolerance (on Utility) 110V-300V (Ph-N) @< 50% LOAD, 110V-176V (Ph-N) @50% - 80% LOAD,
176V-276V (Ph-N) @> 80% LOAD
Input Voltage Tolerance (Bypass) 110-264V (Ph-N)"
OUTPUT
Phase Three Phase with Neutral*
Output voltage 220/230/240V(Ph-N),380/400/415V(Ph-Ph)
AC Voltage Regulation ± 1%
Frequency Range
(Synchronized Range)
46 Hz ~ 54 Hz @ 50 Hz system
56 Hz ~ 64 Hz @ 60 Hz system
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Overload AC Mode 100%~110%: 10 min.
110%~130%: 1 min.
>130% : 1 sec.
Battery Mode 100%~110%: 30 sec.
110%~130%: 10 sec.
>130% : 1 sec.
Current Crest Ratio 3:1 max
Harmonic Distortion 2 % @ 100% Linear Load; 5 % @ 100% Non-linear Load
Transfer
Time
Line Battery
0 ms
Inverter Bypass
0 ms
BYPASS
Automatic Bypass Standard
Manual Maintenance Bypass Standard
Overload on Bypass Continuously working @<130% LOAD, Output off @>130% LOAD for 1min
EFFICIENCY
AC Mode 90% 91% 92%
BATTERY
Type 12V/9AH
Numbers 20 20 x 2 20 x 3
Nominal Voltage 240VDC
Charging Current 2.0 A ± 10% 4.0 A ± 10% (max.)
Charging Voltage 273 VDC ± 1%
Matching Battery Cabinet BP240V135
PHYSICAL
Outline Dimensions,
D X W X H (mm)
592 x 250 x 826 815 x 300 x 1000
Net Weight (kg) 118 178 235
Color RAL 9005
Parallelling Capability N/A Up to 3