15: Inverter R voltage adjustment
Interface Setting
Parameter 1: Will display 15 to represent inverter R voltage.
Parameter 2: Choose Add or Sub to adjust inverter R voltage.
Parameter 3: The voltage range is from 0V to 9.9V.
16: Inverter S voltage adjustment
Interface Setting
Parameter 1: Will display 16 to represent inverter S voltage.
Parameter 2: Choose Add or Sub to adjust inverter S voltage.
Parameter 3: The voltage range is from 0V to 9.9V.
17: Inverter T voltage adjustment
Interface Setting
Parameter 1: Will display 17 to represent inverter T voltage.
Parameter 2: Choose Add or Sub to adjust inverter T voltage.
Parameter 3: The voltage range is from 0V to 9.9V.
18: Output R voltage calibration
Interface Setting
Parameter 1: Will display 18 to represent inverter R voltage.
Parameter 2: Shows OP.V as output voltage*.
Parameter 3: Shows the internal measurement value of the output R voltage. It can be calibrated
by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective upon pressing Enter. The calibration range is limited within +/-9V.
This function is used for parallel operation.
*Does not apply to SUV10KX model.
19: Output S voltage calibration
Interface Setting
Parameter 1: Will display 19 to represent inverter S voltage.
Parameter 2: Shows OP.V as output voltage*.
Parameter 3: Shows the internal measurement value of the output S voltage. It can be calibrated
by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective upon pressing Enter. The calibration range is limited within +/-9V.
This function is used for parallel operation.
*Does not apply to SUV10KX model.
20: Output T voltage calibration
Interface Setting
Parameter 1: Will display 20 to represent inverter T voltage.
Parameter 2: Shows OP.V as output voltage.
Parameter 3: Shows the internal measurement value of the output T voltage. It can be calibrated
by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective upon pressing Enter. The calibration range is limited within +/-9V.
This function is used for parallel operation.
*Does not apply to SUV10KX model.
4. Operation