27
4.11 Warning Code
4. Operation
5. Communication
If errors occur in the UPS but it continues to run normally, the LCD screen will show a warning. In the warning screen, the icon will
flash. Up to 3 error codes may be displayed, each code indicating one error.
Warning code Warning event
01 Battery disconnected
02 IP neutral loss
04 IP phase abnormal
05 Bypass phase abnormal
07 Over charge
08 Low battery
09 Overload
0A Fan failure
0B EPO enable
0D Over-temperature
0E Charger failure
Warning code Warning event
10 L1 IP fuse damaged
11 L2 IP fuse damaged
12 L3 IP fuse damaged
21 Line situations are different in parallel system
22 Bypass situations are different in parallel system
33 Locked in bypass after overload 3 times in
30 minutes
34 Converter current imbalanced
35 Battery fuse damaged
3A Cover of maintenance switch is open
3C Utility power imbalanced
3D Bypass unstable
5.1 RS-232 Port
The RS-232 port is built into the UPS system’s rear panel to provide communication between the UPS and computer. Use Tripp Lite’s
free PowerAlert
®
power management software (available for download at tripplite.com/poweralert) to:
1. Define shutdown delay time (battery shutdown).
2. Perform unmanned shutdown and restart of UPS and computer in the event of an extended utility failure.
5.2 SMART Slot
Install an optional WEBCARDLX in this slot to remotely monitor and control the UPS via a network. The RELAYCARDSV may also be
inserted in this slot to provide dry contact communication functionality. Refer to the WEBCARDLX and RELAYCARDSV manuals for further
details.
Note: Only one card may be used at a time.
5.3 EPO Connector
The EPO is included as standard for site safety. Keep pins 1 and 2 closed for normal UPS operation. To enable EPO function, open
contact between pins 1 and 2.