ROOM VENTILATION
An exhaust fan may be used with the appliance; in each case it shall be installed
in conformity with the appropriate national and local standards. Exhaust hood
operation may affect other vented appliances; in each case it shall be installed in
conformity with the appropriate national and local standards.
TYPE OF GAS
This appliance is shipped from the factory for use with natural gas. For use with
propane LP gas, please follow the conversion procedure described on page 16. A
step by step conversion procedure is also included with each set of LP gas nozzles.
GAS PRESSURE
The maximum inlet gas supply pressure incoming to the gas appliance pressure
regulator is 1/2 PSI.
The minimum gas supply pressure for checking the regulator setting shall be
at least 1˝ w.c (249 Pa) above the inlet specied manifold pressure to the
appliance (This operating pressure is 4˝ w.c. (1.00kPa) for Natural gas and 11˝
w.c. (2.75 kPa) for LP gas.
Gas cooktop requires 1”- 6” side wall spacing above the counter height for
proper combustion. Please review specic model installation instructions for
required dimensions. 30 inches between the cooktop and bottom of the cabinet
above. 0.25 inches for sides below countertop height.
NOTE: Please consult your local building codes for variations with installation.