Tripp Lite PDUMNH32HVAT 7.7kW Single-Phase 200-240V Monitored Automatic Transfer Switch PDU, Two 32A IEC309 32A Blue Inputs, 1 IEC309 32A Outlet, 1U

OWNER’S MANUAL - Page 2

For PDUMNH32HVAT. Series: AG-012F
Also, The document are for others Tripp Lite models: PDUMNH16HVAT, PDUMNH20HVAT, PDUMNH30HVAT

PDF File Manual, 76 pages, Read Online | Download pdf file

PDUMNH32HVAT photo
Loading ...
2
The ATS provides a convenient dongle outlet, but it DOES NOT provide surge or line noise
protection for connected equipment.
The ATS is designed for indoor use only, in a controlled environment, away from excess moisture,
temperature extremes, conductive contaminants, dust or direct sunlight.
The ATS can only be used in a Restricted Access Location where access can only be gained by
qualified service personnel.
Keep indoor ambient temperature between 32°F and 122°F (0°C and 50°C).
The ATS must be installed by a qualified technician only.
Do not attempt to mount the ATS to an insecure or unstable surface.
Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
Connect the ATS to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
Do not power on and use the ATS with one plug exposed.
The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
Do not connect the ATS to an ungrounded outlet or to extension cords or adapters that eliminate
the connection to ground.
Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
Disconnect both AC input sources before servicing ATS unit.
1. Important Safety Instructions
This manual contains information concerning the proper installation
and use of Tripp Lite’s Rackmount Power Strips.
SAVE THESE INSTRUCTIONS.
Do not connect your power strip to an ungrounded outlet. Do not use it with extension
cords or adapters that eliminate its connection to ground. Your power strip is designed
for indoor use only. Install it away from heat emitting devices such as radiators and heat
registers. Do not install where excessive moisture or other conductive contaminants are
present. Never install electrical wiring during a lightning storm.
The power requirement of each device connected to an outlet of your power strip must
not exceed the Outlet Power Rating of your power strip (see Specifications). The total
power requirements of all devices connected to your power strip must not exceed the
Maximum Load Rating of your power strip (see Specifications).
CAUTION Only those who are properly trained or qualified to use this device should
do so. Anyone who is not trained or qualified should not use this device unless it is
under the supervision of someone who is properly trained or qualified to do so.
Children must be supervised to ensure that they do not use the device as a toy.
Never use the device if the cord and plug are damaged; if it is not working properly,
or if it has been dropped or damaged, take it to an authorized service center for
inspection and repair.
If the power cord is damaged, it must be replaced by the manufacturer, its authorized
service agent, or by qualified personnel in order to avoid a danger.
21-06-222-933683.indb 221-06-222-933683.indb 2 11/29/2021 3:56:11 PM11/29/2021 3:56:11 PM