34
Installing and connecting the drain hose of the indoor unit
•Thehosewillbexedpermanentlyintopositionafternishingtheinstallationandthegasleaktest;refertopage
39 for further details.
•Makesuretheinstalleddirectionofthedrainhoseiscorrect.
Inadequate installation may cause condensate water leakage.
•Ifthedrainhoseisroutedinsidetheroom,insulatethehosesothatdrippingcondensationdoesnotdamagethe
furniture or oors.
•DONOTWALLUPTHEDRAINHOSECONNECTION!
Drain hose connection must be easy accessible and serviceable.
•Makesuretheindoorunitisinuprightpositionwhenyoupourwatertocheckforleakage.
Make sure that the water does not overow onto the electrical part.
Change the direction only when it is necessary.
1. Detach the rubber cap with the plier.
2. Detach the drain hose by pulling it and turning to the left.
3. Insert the drain hose by xing it with the screw into the groove of the drain
hose and the outlet of the drain pan.
4. Attach the rubber cap with a screwdriver by turning it to the right until it
xes to the end of the groove.
5. Check for leakage on both side of the drain outlet.
Changing direction of the drain hose
Drain hose
Screw hole
Screw
Rubber cap
Drain pan outlet
Pour the water in direction of arrow.
Direction of the drained water
Vivaldi MAX_AQN09VFU@@ IB&IM_32163A-3_EN.indd 34 2015/8/17 14:47:40