Testing
Test Condensate Pump and Associated Float Switch
following test:
1. Access the electrical control box.
●
2.
3. The pump should start.
4. If the pump does not start, check for voltage at the pump connector on the board. There should be 230 Volts AC to the pump.
If there is not, the circuit board is defective. If there is proper voltage to the pump, either the pump or associated pump wiring
is defective.
2 4
PAGE 35
5.
When installing, the condensate discharge port at the top of the water pump must be connected with drian pipe.