Basic Operation
Accessory Slot: Remove the small cover panel from this slot to
install optional accessories to remotely monitor and control your
UPS. Refer to your accessory’s manual for installation instructions.
Contact Tripp Lite Customer Support at +1.773.869.1234 for more
information, including a list of available SNMP, network management
and connectivity products.
Power Sensitivity Adjustment: This dial is normally set fully counter-
clockwise, which enables the UPS to provide maximum protection
against waveform distortions in its AC input. When such distortion
occurs, the UPS will normally switch to providing sine wave power
from its battery reserves for as long as the distortion is present. In
areas with poor utility power or where the UPS system's input power
comes from a backup generator, chronic waveform distortion could
cause the UPS to switch to battery too frequently, draining its battery
reserves. You may be able to reduce how often your UPS switches to
battery due to moderate waveform distortion by experimenting with
different settings for this dial. As the dial is turned clockwise, the UPS
becomes more tolerant of variations in its input power’s AC waveform.
NOTE: The further the dial is adjusted clockwise, the greater the
degree of waveform distortion the UPS will allow to pass to connected
equipment. When experimenting with different settings for this dial,
operate connected equipment in a safe test mode so that the effect
on the equipment of any waveform distortions in the UPS system's
output can be evaluated without disrupting critical operations.
External Battery Connector (Select Models Only): Use to connect
Tripp Lite external battery packs for additional runtime. Refer to
instructions available with the battery pack for complete connection
information and safety warnings.
Battery Charge Level Switches (Select Models Only): Controls
the UPS system’s battery charge rate. If you connect any external
batteries, set the Battery Charge Level Switch to the down position.
This will increase your UPS system's charger output so the additional
batteries charge faster.
CAUTION!
DO NOT set the Battery Charge Level Switches to the
down position without an external battery connected.
There is a risk of damaging the UPS system's internal
battery system.
Charge Rate Setting
(when External
Batteries are connected)
Charge Rate Setting
(when External Batteries
are not connected)