4. Operation
4.3.6.2.4 BATT Setup
Note: The UPS conguration for the battery cabinet depends on which S3M UPS model and which battery cabinet model are being
connected together. Refer to the S3M-Series battery cabinet manual for specic UPS conguration instructions.
Battery Group: The Battery Group is quantity 1 for every set of 20 batteries that are within the UPS and/or the battery
cabinet connected to the UPS. For example, UPS model S3M100K has no internal batteries. However, to connect one
BP240V100L (40 internal batteries) battery cabinet to the S3M100K UPS, you must congure the S3M100K to Battery
Group 2, and if you connect a second BP240V100L battery cabinet to the S3M100K UPS, update the Battery Group to 4.
The value range is 1 to 8. The default value is 1.
Battery Number: The default value is 20. The battery number must remain at 20 for all S3M10-100K UPS models
whether used with or without external battery cabinets designed for the S3M-Series UPS line.
Single Battery (Ah) Capability: Modify the value to the individual Ah capacity for one battery. The value range is 7 to
2000.
Boost/Float Conversion (Month): Set up the boost charge and oat charge conversion time. The value range is 0 to
24. The default value is 0.
Figure 4-31A: Battery Settings