Tripp Lite S3M60K-60K4T 3-Phase 208V UPS + Input Isolation Transformer Kit - 480V Delta to 208V Wye, 60kVA/kW, External Batteries Required

Owner's Manual - Page 42

For S3M60K-60K4T. Also, The document are for others Tripp Lite models: S3M25K*, S3M30K*, S3M50K*, S3M60K*, S3M80K*, S3M100K*

PDF File Manual, 240 pages, Read Online | Download pdf file

S3M60K-60K4T photo
Loading ...
Loading ...
Loading ...
42
4. Operation
4.3 Alarms, LEDs and the LCD Display
4.3.1 Overview of Audible Alarms and LED Indicators
Audible Alarms Display LEDs
UPS Modes Alarm Status MutableOn/O Alarm Battery Bypass Inverter
UPS Initialization Beeps, 1x No Flashes/0.5s Flashes/0.5s Flashes/0.5s Flashes/0.5s
UPS Online Mode (Normal) No Beeps No Beeps O O O On
UPS Battery Mode Beeps/2s Yes O O On O
UPS Battery Test Mode No Beeps No Beeps O O On O
UPS ECO Mode No Beeps No Beeps O On O O
UPS Standby Mode No Beeps No Beeps O O O O
UPS Static Bypass Mode No Beeps No Beeps O On O O
UPS Maintenance Bypass Mode No Beeps No Beeps O On O O
UPS Frequency Converter Mode No Beeps No Beeps O O O On
UPS Load Overload Beeps/1s Yes O O O Flashes/2s
UPS Warnings Beeps/2s or Beeps/1s Yes Flashes/2s Flashes/2s O On
UPS Faults Beeps/2s or Beeps/1s Yes On On O O
4.3.2 LCD Control Panel Introduction
The built-in LCD display is feature-rich and intuitive to use. The following covers the main features accessible through the
display.
Note: Most settings cannot be changed when the UPS is in inverter mode.
Figure 4-6: Overview of the operating panel of the UPS
1
Alarm LED
2
Bypass LED
3
Battery LED
4
Inverter LED
5
Touchscreen LCD Screen, 5 in. (127 mm)
6
EPO Button (button must be pressed for at least
3 seconds to activate EPO)
1
2
3
4
5
6