Tripp Lite S3M60K-60K4T 3-Phase 208V UPS + Input Isolation Transformer Kit - 480V Delta to 208V Wye, 60kVA/kW, External Batteries Required

Owner's Manual - Page 26

For S3M60K-60K4T. Also, The document are for others Tripp Lite models: S3M25K*, S3M30K*, S3M50K*, S3M60K*, S3M80K*, S3M100K*

PDF File Manual, 240 pages, Read Online | Download pdf file

S3M60K-60K4T photo
Loading ...
Loading ...
Loading ...
26
3. Installation and Wiring
3.10.2 Recommended Circuit Breakers
UPS Model Component Specications
S3M25K
Mains Input Circuit Breaker 100A 3P
Bypass Input Circuit Breaker 100A 3P
Output Circuit Breaker 100A 3P
Battery Circuit Breaker 160A 3P
S3M30K
Mains Input Circuit Breaker 125A 3P
Bypass Input Circuit Breaker 125A 3P
Output Circuit Breaker 125A 3P
Battery Circuit Breaker 200A 3P
S3M50K
Mains Input Circuit Breaker 200A 3P
Bypass Input Circuit Breaker 200A 3P
Output Circuit Breaker 200A 3P
Battery Circuit Breaker 320A 3P
S3M60K
Mains Input Circuit Breaker 250A 3P
Bypass Input Circuit Breaker 250A 3P
Output Circuit Breaker 250A 3P
Battery Circuit Breaker 400A 3P
S3M80K
Mains Input Circuit Breaker 320A 3P
Bypass Input Circuit Breaker 320A 3P
Output Circuit Breaker 320A 3P
Battery Circuit Breaker 600A 3P
S3M100K
Mains Input Circuit Breaker 400A 3P
Bypass Input Circuit Breaker 400A 3P
Output Circuit Breaker 400A 3P
Battery Circuit Breaker 600A 3P
Table 3.3: Recommended Input Front-End and Output Back-End Circuit Breakers
CAUTION!
Protective earth cable: connect each cabinet to the main ground system. For grounding connection,
follow the shortest route possible.
WARNING!
Failure to follow adequate earthing procedures may result in electromagnetic interference or in
hazardsincludingelectricshockandre.
Loading ...
Loading ...
Loading ...