Broan B160H75RT AI Series 160 CFM Heat Recovery Ventilator HRV

USER AND INSTALLER MANUAL - Page 9

For B160H75RT. Series: AI Series
Also, The document are for others Broan models: B110H65RT, B110H65RS, B130H65RT, B130H65RS, B130E65RT, B130E65RS, B150H75NT*, B150H75NS*, B160H75RS, B160H65RT, B160H65RS, B160E65RT, B160E65RS, B150E75NT*, B150E75NS*, B160E75RT, B160E75RS

PDF File Manual, 52 pages, Read Online | Download pdf file

B160H75RT photo
Loading ...
Loading ...
Loading ...
9
2.5 INSTALLING THE EXTERIOR HOODS
Refer to illustration below for an example of proper connection method of the insulated ducts to the hoods. “Anti-Gust Hoods” should
be installed in regions where a lot of snow is expected to fall.
VD0028
EXHAUST
HOOD*
INTAKE
HOOD
B
B
A
A
B
OPTIONAL
DUCT LOCATION
TAPE AND DUCT TIE
CAULKING
CAULKING
LEGEND:
A - SINGLE FAMILY 6 FT
MULTIFAMILY 10 FT
B - 18" OR DEPTH OF EXPECTED SNOW ACCUMULATION
* Do not install exhaust hood with non-return
damper since it can freeze in winter.
Make sure intake hood is located at least 10 feet away from any of the following:
Dryer exhaust, central vacuum vent
Gas meter exhaust, gas barbecue-grill
Any exhaust vents or chimney from a combustion source
Garbage bin and any other source of contamination such as parking lots, streets
For multifamily buildings only:
Make sure exhaust hood is located at least 3 feet away from any of the following:
Property lines
Operable openings into buildings (door, window)
Intake and exhaust hood(s) shall be protected with corrosion-resistant screens, louvers or grilles having openings not less than
1/4 inch and not larger than 1/2 inch.
Install hood(s) at least at 18 inches away from the ground OR depth of expected snow accumulation, whichever is greater.
To minimize cross-contamination of exhausted stale air into the fresh air intake:
Single detached, attached homes and townhouses:
Maintain a 6 feet minimum separation distance between outdoor air intake and exhaust hoods OR use an approved factory-built
intake/exhaust combination termination fitting.
Multifamily buildings:
Maintain a 10 feet minimum separation distance between outdoor air intake and exhaust hoods OR use an approved factory-built
intake/exhaust combination termination fitting.
Ignoring these recommendations could significantly degrade the quality of the incoming air which, in some cases, could result in health
consequences. In the event of a conflict between our recommendations and any local requirements, the latter shall have priority.
WARNING
!