31-5000579 Rev. 2 23
ENGLISH
Dip Switch Setting
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SWO1 is used to set capabilities of main and sub indoor units as well as indoor unit; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Definition and description of SW01
(B) Definition and description of SW03
Note :
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller = communication address + 0 or + 64.
SW03_ 2 = OFF, address of centralized controller = communication address + 0 = communication address SW03_ 2 = ON,
address of centralized controller = communication address + 64 (applies when centralized controller is used and there
are more than 64 indoor units)
• To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1 = ON and SW03_ 2 = OFF;
SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are address codes which are set according to actual
address.
• Address setting function of wired controller for ultrathin card machine is disabled.
SW01_1
SW01_2
SW01_3
SW01_4
Address of wire
controlled indoor unit
[1] [2] [3] [4] Address of wire controlled indoor unit (group address)
0 0 0 0 0# (wire controlled main unit) (default)
0 0 0 1 1# (wire controlled sub unit)
0 0 1 0 2# (wire controlled sub unit)
0 0 1 1 3# (wire controlled sub unit)
0 1 0 0 4# (wire controlled sub unit)
0 1 0 1 5# (wire controlled sub unit)
••• ••• ••• ••• •••• •••
1 1 1 1 15# (wire controlled sub unit)
SW01_5
SW01_6
SW01_7
SW01_8
Capability of indoor unit [5] [6] [7] [8] Capability of indoor unit
0 0 0 0 0.6HP (MVAO005ME2AA)
0 0 0 1 0.8HP (MVAO007ME2AA)
0 0 1 0 1.0HP (MVAO009ME2AA)
0 0 1 1 1.2HP (MVAO012ME2AA)
SW03_1 Address of setting
mode
[1] Address setting mode
0 Automatic setting (default)
1 Code-set address
SW03_2
~
SW03_8
Code-set indoor unit
address and centralized
controller address
[2] [3] [4] [5] [6] [7] [8] Address of indoor unit Address of centralized controller
0 0 0 0 0 0 0 0# (Default) 0# (Default)
00000011# 1#
00000102# 2#
••• ••• ••• ••• ••• ••• ••• ••• •••
0 1 1 1 1 1 1 63# 63#
1 0 0 0 0 0 0 0# 64#
1 0 0 0 0 0 1 1# 65#
1 0 0 0 0 1 0 2# 66#
••• ••• ••• ••• ••• ••• ••• ••• •••
1 1 1 1 1 1 1 63# 127#
ELECTRICAL WIRING