14 31-5000579 Rev. 2
ENGLISH
INSTALLATION INSTRUCTIONS
Ceiling Suspending
Situation with New Ceiling:
(1) Install the indoor unit temporarily:
attach the hoisting foot to hoisting stud. Make sure that nuts and washers should be used at two ends of the foot to
secure the foot.
(2) For the size of the ceiling hole, please refer to the schematic drawing at the previous page.
(3) Adjust the unit to the proper installation location.
(4) Check if the unit is in the horizontal level:
The indoor unit is equipped with a built-in drainage pump and a floater switch. Check if the 4 angles of the unit are in
the horizontal level with the water level or the polythene tube with water, as shown in the figure,taking only one indoor
unit as an example. If the unit inclines opposite to the
direction of condensate flow, the floater switch might
have faults, causing water dropping. (When lifting can be
tilted to the drain, the long side of the horizontal height
difference 0 ~ 0.4in (10mm).)
(5) Tighten the nut on the washer.
(6) Remove the mounting cardboard.
Situation with Original Ceiling:
(1) Install the indoor unit temporarily: attach the hoisting
foot to hoisting stud. Make sure that nuts and washers
(provided on site) should be used at two ends of the foot
to secure the foot.
(2) Adjust the height and location of the unit.
(3) Perform Step 4 and 5 in Situation with New Ceiling.
Preparation of Decorated Panel P1B-1050IB1:
DO NOT put the decorative panel facing down on the floor to avoid scratches.
DO NOT put the decorative panel against wall or any sharp objects.
DO NOT touch the louver or apply force on it or the louver will have defects.
(1) Check the level of the indoor unit with a flat or filled polyethylene pipe and check that the size of the ceiling hole is
correct. Remove the horizontal gauges before installing the panels.
(2) Fix the screws so that the height difference between the two sides of the indoor unit is less than 0.2in (5mm).
The installation of the decorative panel in the indoor unit body:
Remove the return air plate before installing the panel. Press buttons on both ends and slowly pull the return air plate off.
Place it properly to avoid scratches to its surface.
Make sure installing the panel in the correct orientation as show in
picture below.
Remove the air filter. Snap tabs of the panel into the hooks of the
indoor unit on both sides. Open the screw cover to expose the holes
and then install the screws. Close the screw hole cover after the
installation is complete.
Water level or Polythene tube
Nut (provided on site)
Washer
WasherHoisting foot
Tightening (dual nuts)
[Secure hoisting foot] [Secure washer foot]