LG Electronics 705371 LG Dual Zone Mini Split Air Conditioner System with 48000 BTU Cooling Capacity, 2 Indoor Units, and Outdoor Unit

User Manual - Page 52

For 705371.

PDF File Manual, 80 pages, Read Online | Download pdf file

705371 photo
Loading ...
Loading ...
Loading ...
52
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Y-Branch Kit Insulation
Each Y-branch kit comes with clam-shell type peel-and-stick insulation jackets molded to fit the Y-branch fittings—one for the liquid line, one
for the vapor line.
Check the fit of the Y-branch clam-shell
insulation jacket after the Y-branch is
installed.
Mark the pipe where the insulation jacket
ends.
Remove the jacket.
Install field-provided insulation on the pipes
first.
Peel the adhesive glue protector slip and
install the clam-shell jacket over the fitting
Liquid and Gas
Pipe Joints
Y-Branch Kit Insulation
Insulation for
Field-Installed Piping
Field-Supplied Insulation Tape
Figure 70: Y-branch Insulation Detail.
Additional Insulation for Y-Branches May be Required in Humid Environments.
,IWKHV\VWHPKDVEHHQRSHUDWLQJIRUDORQJWLPHLQDKLJKKXPLGLW\HQYLURQPHQWGHZSRLQWWHPSHUDWXUHPRUHWKDQ)FRQGHQVDWHLVOLNHO\
to form. If this happens, install 3/8 inch thick ethylene propylene diene methylene (EPDM) insulation that is plenum-rated with a heat-resistance
factor that follows applicable local, state, and federal codes.
Refrigerant Piping Insulation
REFRIGERANT PIPING PREPARATION
Loading ...
Loading ...